The dimensions are given in mm. Fig. 1.1 Dimensions of the indoor unit. Legend H Height L Length D Depth MODEL V 10-025 NHI V 10-035 NHI Table 1.1 Dimensions and weights of the indoor unit. Split Type Installation Manual...
1 Dimensions Outdoor Unit The outdoor unit ensures that the absorbed air is released to the outside from the room during operation in cooling mode and that the heat introduced into the room during operation in heat pump mode is taken from the outside.
Dimensions 1 Accesories 2 General Installation Diagram Fig. 1.3 General diagram of the installation and the minimum assembly distances. (MONO). Legend Indoor Unit 2 Outdoor Unit 3 Pipe for draining the condensed water A Front separation (minimum 10 cm) B Top separation in relation to the ceiling (minimum 5 cm) D Height in relation to the floor (minimum 2 m) E Side separation opposite side connections (minimum 10 cm) F Rear separation (minimum 10 cm)
3 Connecting Diagram Connecting Diagram Fig. 3.1 Wiring indoor unit. Electric Characteristics V 10-025 NW V 10-035 NW Voltage (V/Ph/Hz) 230/1/50 230/1/50 Supply section up to 25 meters (in mm Indoor / Outdoor Indoor Indoor Thermal-magnetic circuit breaker, type D (A) Interconnection section up to 25 meters (mm Inteconnect Shield or not (YES/NO) Immediatte residual current protector (A)
Technical specifications 4 Technical Specifications Units V 10-025 NW V 10-035 NW Indoor Unit V 10-025 NHI V 10-035 NHI Outdoor Unit V 10-025 NHO VH 10-035 NHO 2,70 3,55 Cooling Capacity 9.215 12.115 Fg/h 2.322 3.053 Power input 0,84...
Page 8
Additional charge per meter Table 4.1 Technical specifications V 10-025 / 035 NW Note! As part of its policy for ongoing improvements of its products, Vaillant reserves the right to modify these specifications without prior notice. Split Type Installation Manual...
7 Service Diagnosis Service Diagnosis Caution for Diagnosis The operation lamp flashes when any of the following errors is detected. 1. When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions, disabling equipment operation. 2.
Service Diagnosis 7 Error Codes and Description indoor display Code indication Description Outdoor Indoor (LED1 flash times) Indoor and Outdoor Communication fault between indoor and outdoor units Room temperature sensor failure Heat-exchange sensor failure Indoor Indoor EEPROM error Malfunction Indoor fan motor malfunction High work-intense protection Outdoor EEPROM error The protection of IPM...
7 Service Diagnosis 7.3.1 Thermistor or Related Abnormality (indoor unit) E1: Room temperature sensor failure Indoor Display E2: Heat-exchange sensor failure Troubleshooting Caution! Be sure to turn off power switch before connect or disconnect connector, or else parts damage may be occurred. Fig.
7 Service Diagnosis 7.3.3 IPM protection outdoor display LED1 flash 2 times,Indoor display F11. Caution! Be sure to turn off power switch before connect or disconnect connector, or else parts damage may be occurred. Fig. 7.3 Flow chart. Split Type Installation Manual...
Service Diagnosis 7 Check the IPM module method: Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the connector, press the protrusion on the connector. Then, to measure resistance between P(+) andN(-) and the U, V and W terminals of the compressor connector with a multi-tester.
Service Diagnosis 7 7.3.6 Overheat Protection For Exhaust Temperature Indoor display outdoor display LED1 flash 8 times Fig. 7.6 Flow chart. Split Type Installation Manual...
Service Diagnosis 7 7.3.10 Power Supply Over or under voltage fault Indoor Display Outdoor display LED1 flash 6 times Fig. 7.10 Flow chart. About how to check the IPM module,please refer to IPM protection fault Split Type Installation Manual...
7 Service Diagnosis 7.3.11 Loop of the station detect error Indoor Display Fig. 7.11 Flow chart. 7.3.12 Over-current of the compressor Outdoor Display LED1 flash 24 or 25 times Fig. 7.12 Flow chart. Split Type Installation Manual...
PCB Explanation 9 PCB Explanation Select the wind volume when it is set automatic When the wind volume is automatic, it can be switched Functions and Control between strong, medium and weak according to the temperature adjusting levels. Wind volume under the 9.1.1 Main functions and control specification of automatic wind volume mode.
Page 34
9 PCB Explanation • The fan motor works as set if the he heat exchange temperature remains 35 ºC for more than 4 minutes • The fan motor works as set if the he heat exchange temperature remains above 38 ºC. When the compressor stops and remains idle for 3 minutes 20 seconds after the compressor stops, the up wind...
PCB Explanation 9 The operation mode may switch between the cooling Powerful cooling and heating according to the indoor temperature under Change the set temperature. With temperature adjusting the automatic mode. If the unit is under the cooling function. mode currently, when the temperature is enough for the compressor to stop, the compressor stops.
9 PCB Explanation Sleeping function Rated Operation a. After setting the sleeping function, the refrigerating When receiving the instruction of indoor Rated mode and dehumidification mode will run as per the unit rated operation, the unit will start Cooling: following rules: rated cooling operation.
PCB Explanation 9 Compressor Frequency Increase/Decrease Speed 9.2.4 Outdoor Defrosting Control Rapid Frequency Increase/ 1Hz/s Defrosting Mode Entry Conditions Decrease Speed 1 The unit will enter defrosting mode when compressor starts Slow Frequency Increase/ up and operates for 10 minutes continuously in heating mode 1Hz/10s Decrease Speed 2 or after compressor runs for an accumulated time of 45...
9 PCB Explanation When defrosting exit conditions are met, the unit will Indoor Heat Exchanger Anti-freeze Protection operate as follows Compressor stops and external fan starts, 50s later, four-way valve will be on, 60s later, compressor will operate as per startup process. 9.2.5 PTC Output Control When outdoor unit is energized, PTC output value is 0, 10s later, output value is 1.
PCB Explanation 9 Function of Main Thermistor 2. The indoor heat exchanger thermistor is used for preventing freezing.During the cooling operation, if the temperature drops abnormally, the operating frequency becomes lower, then the operation halts. 3. The indoor heat exchanger thermistor is used for anti-icing control.During the cooling operation, if the heat exchanger temperature in the room where operation is halted becomes -1°C, it is assumed as...
Page 55
Vaillant pridržava pravo na izmjene bez najave. Vaillant si riserva il diritto di apportare modifiche senza preavviso. Vaillant behoudt zich het recht voor om veranderingen aan te brengen zonder voorafgaande kennisgeving. Vaillant önceden uyarı yapmaksızın değişiklik yapma hakkını saklı tutmaktadır.
Page 56
Kent ME2 4EZ Telephone 0164 292300 Fax 0164 290166 www.vaillant.co.uk info@vaillant.co.uk Vaillant Isi Sanayi ve Ticaret Ltd. Sti. Müsteri Hizmetleri: 444 2 888 Bahçelievler Mah. Bosna Bulvari No: 146 Çengelköy-Üsküdar / Istanbul Tel: (0216) 558 80 00 Fax: (0216) 462 34 24 www.vaillant.com.tr...
Need help?
Do you have a question about the V 10-025 NHI and is the answer not in the manual?
Questions and answers