Power Requirements; Shipping And Storing Components - Dell C7004/C150 Installing And Maintaining

Table of Contents

Advertisement

Power Requirements

There are two types of power supplies: Power Supply 1200W-AC and Power Supply 1600W-AC. The
minimum and the redundant power supplies required to operate is listed in the table below. Dell
Networking recommends the redundancy configuration.
Power Supply 1200W-AC/Power Supply
1600W-AC
Power Supply 1200W-AC
Power Supply 1600W-AC
The C7004/C150 needs at least one power supply to operate. However, Dell Networking recommends a
one-plus-one redundancy configuration. That is, use a minimum of two AC or DC power supplies; one is
for redundancy.
The C7004/C150 power requirements are given below:
Table 3-1. System Specifications
Parameter
Nominal Input Voltage
Maximum AC Power Supply Input Current
(Based on 1200 W output for 100/120 V and
1600 W 200/240 V lines)
Maximum System Power Input
Maximum Thermal Output at 100/120V
Maximum Thermal Output at 200/240V

Shipping and Storing Components

If you do not install your C7004/C150 system and components immediately, Dell Networking
recommends you properly store components (including all extra field-replaceable parts) until you are
ready to install them.
Follow these indoor storage guidelines:
• Storage temperature should remain constant ranging from -40°F to 158°F (-40°C to 70°C).
• Non-condensing relative humidity should be maintained with 5 to 95%.
• Store on a dry floor, away from direct sunlight, heat, and air conditioning ducts.
• Store in a dust-free environment.
12
|
Preparing the Site
Voltage
Minimum PSUs
100-120
1
200-240
1
200-240
1
Minimum with
Redundant PSUs
2
2
2
Specifications
100-240 V 50/60 Hz
14 A @ 100 V per AC Power Supply
11 A @ 120 V per AC Power Supply
9 A @ 200 V per AC Power Supply
7 A @ 240 V per AC Power Supply
6,897 KVA @ 100/120 V
7,315 KVA @ 200/240 V
5,618 BTU/hour
5,304 BTU/hour