Laars OMNITHERM ONH1250 Assembly, Installation And Operation Instructions page 114

Boiler water heater
Table of Contents

Advertisement

Page 114
Error Codes (continued)
Condition
Inlet Sensor
Burner
Parasitic
Flame
Burner Max
Trials
Additional
High Limit
Information
Inlet sensor is damaged or not
connected.
Manual-reset condition
Annunciation – on Navigation Bar
Lockout: Inlet Probe
Sensing flame on burner prior to
ignition.
Manual-reset Condition
Annunciation – on Navigation Bar
Lockout: Burner Parasitic Flame
The maximum attempts for ignition
has occurred, without sensing
flame.
Manual-reset Condition
Annunciation – on Navigation Bar
Lockout: Burner Max Trials
Outlet water temperature has
exceeded the additional high limit
setting
Auto-reset Condition
Annunciation – "Warning Additional
high limit" on Message Screen
LAARS Heating Systems
Corrective Action
122
3563
140
2463
158
1739
176
1253
194
919
212
685
Check the sensor and wiring.
Repair or replace as needed.
Measure the resistance of the
sensor and compare to the
resistance table below. Replace
if necessary.
Temp
Temp
Resistance
(°F)
(°C)
(Ω)
68
20
86
30
104
40
122
50
140
60
158
70
176
80
194
90
212
100
Inspect flame and wiring for
damage and continuity. Replace
if necessary.
Verify supply and manifold gas
pressures satisfy installation
requirements.
Verify the proper intake and
venting.
Inspect the burner.
Check pilot and main valve
wiring and operation.
Check ignition transformer
electrode, flame detector wiring
and position.
Verify the system is full of water
and all air has been purged from
the system.
Verify the boiler/heater is piped
properly into the heating system.
Check for proper pump
operations.
Check the additional high limit
set point.