Laars OMNITHERM ONH1250 Assembly, Installation And Operation Instructions page 113

Boiler water heater
Table of Contents

Advertisement

O
T
The
MNI
HERM
Condition
Condensate
Level
Outlet
Sensor
Outlet
Sensor Drift
Information
Lockout: Low Gas Pressure
Condensate trap water level is high
Auto-reset Condition
Annunciation – "Warning
Condensate level" on Message
screen
Outlet probe is not connected
Manual-reset Condition
Annunciation – on Navigation Bar
Lockout: Outlet Probe
Dual element sensor readings do
not agree.
Manual-reset Condition
Annunciation – on Navigation Bar
Lockout: Outlet Probe Drift
Corrective Action
Verify supply and manifold gas
pressures satisfy installation
requirements.
Check condensate trap for
proper drainage
Check condensate trap for stuck
level switch
Check the sensor and wiring.
Repair or replace as needed.
The outlet probe is a dual
element probe with 10K and 20K
thermistors. A quick test is to
measure resistance and verify
one resistance is double the
other. Replace if necessary.
Measure the resistance of each
element of the sensor and
compare to the resistance table
below. Replace if necessary.
10K
Temp
Resistance
(°F)
(Ω)
68
12555
86
8025
104
5279
122
3563
140
2463
158
1739
176
1253
194
919
212
685
Check the sensor and wiring.
Repair or replace as needed.
The outlet probe is a dual element
probe with 10K and 20K
thermistors. A quick test is to
measure resistance and verify one
resistance is double the other.
Replace if necessary.
Measure the resistance of each
element of the sensor and compare
to the resistance table below.
Replace if necessary.
10K
Temp
Resistance
(°F)
(Ω)
68
12555
86
8025
104
5279
Page 113
20K
Resistance
(Ω)
25099
16057
10569
7139
4937
3489
2514
1845
1376
20K
Resistance
(Ω)
25099
16057
10569