Download Print this page

Mitsubishi Electric Mr.SLIM MSY-GR09VF Operating Instructions Manual page 12

Hide thumbs Also See for Mr.SLIM MSY-GR09VF:

Advertisement

Available languages

Available languages

● OPERATING INSTRUCTIONS ●
E
RROR CODE DISPLAY MODE
Error code can be checked on the display of remote
controller while the upper operation indicator lamp
on the indoor unit is blinking.
Fo llow the procedure b el ow to check the error code.
An example of error code (00)
1
Error code display
• The remote controller is powered OFF.
• Get close t o the f ront of the indoor unit (within 2 m) , point the remo te
contr oller at the rec eiving section of indoor unit, and keep pressing the
CHE CK with a fine-tipped obj ect until the display of remote controller
turns off.
• K eep point ing the remote controller at the receiving section of indoor
unit, until the error code (2 digits) appears on the display after the
indoor unit beeps.
2
Error code check
• If "--" a ppears on the display, it mean s the remote contr oller has not
recei ved the si gnal fr om the indoor unit. Press any bu tton to cancel the
error code display mode. Get closer to the indoor unit, and try again.
If the remote controller still can not receive it, please turn off the noise
source (fl uorescent lamp, TV etc.).
• "00" appears on the display when there is no error.
• When an error code (other than "00") app ears on the display, the air
conditioner needs to be inspected and repa ired. Stop using the air
conditioner, turn off the breaker and contact your dealer.
Note:
• Any button can cancel the error cod e display mode of the remote controller.
• Proper er ror code may not appear if the er ror code is checked while the opera-
tion indicator lamp is not blinking.
En-11
"- -" appears on the display when the
remote controller cannot receive the
signal from the indoor unit.
Error code of remote controller
Object
Code
Abnormal point
00
None (Normal)
Ind oor unit
E6
Serial signal
E7
Fb
Indoor control system
P1
Room temperature thermistor
P2
Indoor coil thermistor
P9
Pb
Indoor fan motor
Outdoor unit
E8
E9
Indoor/outdoor communication, receiving error
EC
FC
Nonvolatil e memory data
Fd
Di fferent voltage
P8
4-way valve/Pipe temperature
PL
Outdoor refrigerant system
U3
Discharge temper ature thermistor
Defrost thermistor
F in temperature thermistor
U4
P.C. board temp erature thermistor
Ambient temperature thermistor
Outdoor heat ex changer temperature thermistor
UE
Stop val ve (Closed valve)
UP
Outdoor power system

Advertisement

loading