XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Changing the access level 2 entry code
This function allows you to change the four digit code needed to activate the panel's access level 2
menu options. When selected, press the Accept6 button and the following window will appear:
Enter NEW Access Level 2 Code
5
4
Using the
(1),
fourth digit has been entered, the panel will request you confirm the new code by re-entering it.
Enter NEW Access Level 2 Code: ****
Confirm NEW Access Level 2 Code:
Enter the code again by pressing the
codes match, the panel will accept the code and you will be taken back to access level 2. If you type
an incorrect confirmation code you will be prompted to start the new code entry sequence again.
BE SURE TO KEEP A RECORD OF THE NEW CODE ON PAGE 20 OF THIS USER MANUAL.
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000510 Rev 1 • Page 19 of 28