2-7 Inverter Operation:

To operate the power inverter, turn it on using the ON/OFF switch on the front panel.
The power inverter is now ready to deliver AC power to your loads.
If you are operating several loads from the power inverter, turn them on separately
after the inverter has been turned on.
This will ensure that the power inverter does not have to deliver the starting currents
for all the loads at once.
2-7-1 Controls and indicators:
The ON / OFF switch turns the control circuit in the power inverter on and off.
The PSW2KVA/E Inverter operates from an input voltage ranging from:
10.0 to 16.0 VDC for 12V models
20.0 to 32.0 VDC for 24V models
42.0 to 62.0 VDC for 48V models
90.0 to 140.0VDC for 110V models
180.0 to 275.0VDC for 220V models
The PSW2KVA/E Inverter will indicate high and low DC voltage conditions as follows:
Model
voltage shut-down
RM-PSW122KVA
RM-PSW122KVAE
RM-PSW242KVA
RM-PSW242KVAE
RM-PSW482KVA
RM-PSW482KVAE
RM-PSW1102KVA
RM-PSW1102KVAE
RM-PSW2202KVA
RM-PSW2202KVAE
2-7-2 Output Voltage Indicator:
LED displays light on VAC as show as output Voltage value
2-7-3 Output Current Indictor
LED displays light on AMP as show as output current value
2-7-4 Output Watts Indictor
LED displays light on Watts as show as output Watts's value
2-7-5 Input DC Voltage Indictor
LED displays light on VDC as show as input DC voltage value
2-7-6 Temperature Indictor
LED displays light on TEMP as show as internal operating temperature value
2-7-7 Output Frequency DC Indictor
LED displays light on Hz as show as output frequency value
DC Input over
DC Input over
voltage alarm
16.0VDC
15.5VDV
32.0VDC
31.0VDC
62.0VDC
61.0VDC
140VDC
135VDC
275VDC
270VDC
DC Input under
voltage alarm
10.5VDC
21.0VDC
43.0VDC
95VDC
185VDC
12
DC Input under
voltage shut-down
10.0VDC
20.0VDC
42.0VDC
90VDC
180VDC

Advertisement