Hotel Mode Setting; Power Saving Details Setting - Hitachi PC-ARFG-E Installation & Operation Manual

Wired remote controller
Hide thumbs Also See for PC-ARFG-E:
Table of Contents

Advertisement

SERVICE & INSTALLATION MENU
5 Press " " or " " to select "Save" and press "OK" to change
password.
Select "Not Save", the screen returns to Step3.
Press " ", the screen returns to Step2.
6 Press "OK", the screen returns to Step2.

Set Password Input Effective Time
1 Select "Service Menu" on the Service & Installation screen
and press "OK".
2 Select "Password Setting" and press "OK".
3 Select "Effective Time"and press "OK".
4 Press " " or " " to select the setting item and press "OK" to
confirm the setting. The item changes as follows:
"Everytime" ↔ "10 min" ↔ "30 min" ↔ "60 min" ↔ "120 min".
Press " " and it returns to Step3.
?
N O T E
The default password is "0000", and the supervisor code is "5567".
If you forget the password, use the supervisor code to change the
password.
The supervisor code can't be changed.
For two remote controllers, the passwords are not synchronized
automatically. For each remote controller, the password needs to be
set individually.
74
PMML0565 rev.1 - 04/2022

6.2.3 Hotel Mode Setting

This setting enables or disables the hotel mode.
1 Select "Service Menu" on the Service & Installation screen
and press "OK".
2 Select "Hotel Mode" and press "OK".
3 Press " " or " " to select enabled setting.
4 After selecting, press "OK".
5 Select "Yes" and press "OK" to confirm the settings and
display the completion screen.
6 If you select "Cancel", the screen returns to Step3.
?
N O T E
Refer to "Hotel Mode Setting" in

6.2.4 Power Saving Details Setting

This chapter provides the details about the available settings
related to the power saving function.
There are 3 power saving modes available: outdoor unit capacity
control, indoor unit rotation control and intermittent control.
Settings for these 3 power saving modes are available from this
menu.
?
N O T E
Go to Power Savings Setting from Function Menu. Also refer to "Power
Savings Setting" in
"5.3.1 Power Savings Mode Setting"
Item
Capacity control deals with the outdoor unit
capacity, the aim of the function is to reduce the
Capacity Control
running current of the system to match with the
capacity control setting. Set control mode and
power savings level with its corresponding value.
Interlock with indoor units of the same outdoor
Rotation Control
unit system and switch to FAN operation in
sequence. Set control mode and fan mode time.
Cooling/heating mode and fan mode are
Intermittent Control
repeated at regular intervals. Set power savings
level.
Reset Default
Initialize the power saving settings.

Outdoor Capacity Control Setting
Item
The "Peak Cut Control" reduces the power
consumption range when it exceeds the value of
the power setting. On the basis of the current air
Control Method
conditioning capacity, the "Moderate Control" is
used to moderate the air conditioning capacity
as well as the peak.
Assign the corresponding capacity control values
Power Savings
to the low, medium, and high power savings
(Low/Med/High)
levels.
Change Level
The power saving level can be set.
"9 Hotel Mode
Setting".
for details.
Function
Description