Setting Up; Instrument Power-Up - ABB C1900RC Operating Manual

Circular chart recorder/controller
Hide thumbs Also See for C1900RC:
Table of Contents

Advertisement

2 SETTING UP

2.1 Instrument Power-up – Fig. 2.1 and 2.2
Caution. Ensure that all connections, especially to the
earth stud, are made correctly.
a) Check that the input sensors are installed correctly.
b) Check that the pen(s) are installed correctly – see Fig. 2.1.
c) Switch on the supply to the instrument, any power-operated
control circuits and the input signals. Wait for the pens to
settle.
Note. On power-up, the pens are moved to an off-
chart position for automatic referencing. Pen chatter
may occur on those pens nearest the reference
position.
This is a normal function of the instrument.
d) The start-up sequence shown in Fig. 2.2 is displayed on
faceplate 1 when the supply is first switched on.
0.175 (4.4)
0.35 (8.8)
Note. If the true time line event option is fitted, the
violet event pen records on the same time line as
the red pen, but on the outer edge of the chart.
Fig. 2.1 Checking the Pen(s) Installation
LINE
FAILEd
AL
RMT
Lined Failed indicates power failure
and is cleared when advancing to the
next frame or page.
2
Blue Pen
(Channel 3)
Red Pen
(Channel 1)
Green Pen
(Channel 2)
Black Pen
(Channel 4)
– see
Note
Chart Time Line
0.175 (4.4)
Dimensions in inches (mm)
Flashing
between
AT
MAN
Fig. 2.2 Instrument Displays at Start-up
1914 r
tESt
Instrument Test identifies the instrument type, e.g.
1914r – see Table 2.1 in the
CPU
or
PASS
CPU Test carries out check of processor circuitry – see
below.
Error Codes
CONFIG
or
PASS
Configuration Test carries out check of non-volatile
memories containing the instrument configuration, then
indicates pass or fail – see
CAL
or
PASS
Calibration Test carries out check of non-volatile
memories containing the calibration data for each analog
input and output, then indicates pass or fail – see
below.
Codes
bb rAM
or
PASS
Battery Back RAM Test carries out check of battery-
backed RAM, then indicates pass or fail – see
below.
Codes
!00. 3
or
100. 3
AL
RMT
AT
MAN
Normal Display
Not applicable on single
channel instruments
Installation Manual.
CPU
FAIL
CONFIG
FAIL
below.
Error Codes
CAL
FAIL
Error
bb rAM
FAIL
Error
A––––F
–2–4––
Error Codes are
displayed in the event
of a fault – see Section
2.1.1.

Advertisement

Table of Contents
loading

This manual is also suitable for:

C1900

Table of Contents