Control Page (Heat/Cool Control) - ABB C1900RC Operating Manual

Circular chart recorder/controller
Hide thumbs Also See for C1900RC:
Table of Contents

Advertisement

...5 CONTROL OPERATION

5.10.1 Control Page (Heat/Cool Control)

CONtrL
PAGE
CYCt
h 300. 0
h
1. 0
h
PrOP
h 999. 9
h 100. 0
h
h
h 7200
INtGrL
h
h
OFF
h
Integral
Off
MrESEt
h 100. 0
h
50. 0
h
CYCt
c 300. 0
c
1. 0
c
PrOP
c 999. 9
c 100. 0
c
c
c 7200
INtGrL
c
c
OFF
c
32
Page Header – Control Page
Cycle Time (heat output)
This setting can be ignored for analog control outputs.
1. 0
Set the required cycle time for time proportioning control, from 1.0 to 300.0 in 0.1
second increments (300 seconds = 5 minutes).
Proportional Band (heat output)
Set the proportional band value required, between 0.1 and 999.9% in 0.1%
0. 1
increments.
OFF
Integral Action Time (heat output)
1
Set the required time between 1 and 7200 in 1 second increments (7200 seconds =
OFF
120 minutes). 'OFF' is selected below 1 and above 7200.
Manual Reset (heat output)
Set the required proportional band offset on the lower display, between 0.0 and
0. 0
100.0% of the engineering range span in 0.1% increments.
Cycle Time (cool output)
This setting can be ignored for analog control outputs.
1. 0
Set the required cycle time for time proportioning control, from 1.0 to 300.0 in 0.1
second increments (300 seconds = 5 minutes).
Proportional Band (cool output)
Set the proportional band value required, between 0.1 and 999.9% in 0.1%
0. 1
increments.
OFF
Integral Action Time (cool output)
1
Set the required time between 1 and 7200 in 1 second increments (7200 seconds =
OFF
120 minutes). '
Continued on next page.
OFF
' is selected below 1 and above 7200.