Refrigerant Piping System Layout - LG Art Cool Premier LA120HYV1 Installation Manual

Single zone wall mounted
Hide thumbs Also See for Art Cool Premier LA120HYV1:
Table of Contents

Advertisement

GENERAL INSTALLATION GUIDELINES

Refrigerant Piping System Layout

Pipe Sleeves at Penetrations
LG requires that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an
appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and free movement of the pipe within the sleeve
(Figure 26). Underground refrigerant pipe shall be routed inside a protective sleeve to prevent insulation deterioration. Refer to Figure 27.
Figure 26: Pipe Sleeve Options.
Diameter of penetrations shall be determined by pipe diameter plus the thickness of the insulation.
Underground Refrigerant Piping
Refrigerant pipe installed underground should be routed inside a
vapor tight protective sleeve to prevent insulation deterioration and
water infiltration. Refrigerant pipe installed inside underground
casing must be continuous without any joints. Underground
refrigerant pipe must be located at a level below the frost line.
Table 12: Utility Conduit Sizes.
Liquid Pipe
1
3/8 (1-1/8
1/4 (1.0)
4
3
3/8 (1-1/8)
4
3
OD pipe diameter in inches; Values in parenthesis () indicate OD of pipe with insulation jacket.
1
Diameter of pipe with insulation. Thickness of pipe insulation is typical. Actual required thickness may
2
vary based on surrounding ambient conditions and should be calculated and specified by the design
engineer.
Insulation thickness (value in parenthesis) = 3/8 inch.
3
Insulation thickness (value in parenthesis) = 1 inch.
4
28
Vapor Pipe
1
)
1/2 (2.0
)
5/8 (2-1/8
2,3
2,4
4
4
4
4
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 27: Typical Arrangement of Refrigerant Pipe and Cable(s) in a
Utility Conduit
)
2,4
Table 13: Heat Pump Unit Refrigerant Pipe Connections
(All Brazed Type)
Model
LAU090HYV1, LAU120HYV1
LAU180HYV1, LAU240HYV1
Vapor Line
Insulation Material
Liquid Line
Pipe Sleeve
Insulation
Material
Min. 18 Gauge
Power/Communication
Cable
Liquid Conn.
Vapor Conn.
(inches)
(inches)
1/4
3/8
3/8
5/8