Electrical - LG Art Cool Premier LA120HYV1 Installation Manual

Single zone wall mounted
Hide thumbs Also See for Art Cool Premier LA120HYV1:
Table of Contents

Advertisement

Table 2: Art Cool Premier Electrical Data
Nom.
Unit Model Nos.
Tons
Art Cool Premier
LA090HYV1
3/4
LA120HYV1
1
LA180HYV1
1-1/2
LA240HYV1
2
For component model nos.
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity
ODU Fan = Outdoor Unit Fan Motor
Table 3: Art Cool Premier Models
Compressor
Compressor(A)
Qty
Cool/Heat
1
8.3/8.3
1
8.3/8.3
1
14.5/14.5
1
14.5/14.5
IDU Fan = Indoor Unit Fan Motor
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down
to the nearest standard fuse size.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Fan Qty
ODU Fan(A)
IDU Fan(A)
1
0.40
1
0.40
1
0.50
1
0.50
GENERAL DATA

Electrical

MCA(A)
MOP(A)
0.40
11.2
15
0.40
11.2
15
0.30
19.0
25
0.30
19.0
25
11