R410A Refrigerant - LG Art Cool Premier LA120HYV1 Installation Manual

Single zone wall mounted
Hide thumbs Also See for Art Cool Premier LA120HYV1:
Table of Contents

Advertisement

GENERAL DATA

R410A Refrigerant

R410A Refrigerant - 0% Ozone Depleting
R410A refrigerant has a higher operating pressure in comparison to R22 refrigerant and, therefore, all piping system materials installed must
have a higher resisting pressure than the materials traditionally used in R22 systems.
R410A refrigerant is an azeotrope of R32 and R125, mixed at 50:50, so the ozone depletion potential (ODP) is 0.
Do not place the refrigerant cylinder in direct sunlight. Exposure to direct sunlight can cause the refrigerant cylinder to explode,
resulting in death or severe injury.
• Piping wall thickness must comply with the applicable local, state, and federal codes for the 551 psi design pressure of R410A.
Do not use any piping that has not been approved for use in high-pressure refrigerant systems.
Do not heat refrigerant piping more than necessary during installation. Excessive heat can cause the pipe to soften.
• Because R410A is a combination of R32 and R125, the required additional refrigerant must be charged in its liquid state. If the refrig-
erant is charged in its gaseous state, its composition changes and the system will not work properly.
12
Due to our policy of continuous product innovation, some specifications may change without notification.