Installation & Layout Best Practices; Refrigerant Piping System Layout; Refrigerant Piping System Layout - LG Art Cool PREMIER Engineer's Manual

Art cool premier wall mounted 3/4 and 1 ton
Hide thumbs Also See for Art Cool PREMIER:
Table of Contents

Advertisement

inStallation & layout bESt praCtiCES

Refrigerant Piping System Layout

definitions
Physical Pipe Length: Actual length of straight segment(s) of pipe.
Equivalent Pipe Length: Actual length of pipe plus equivalent
lengths of elbows and valves.
layout procedure
1. Draft a one-line diagram of the proposed piping system connect-
ing outdoor unit to indoor unit. Follow the pipe limitations listed.
2. Calculate the physical length of each pipe segment and note it on
the drawing.
3. Calculate the equivalent pipe length of each pipe segment.
using Elbows
Field-supplied elbows are
allowed as long as they are
designed for use with R410A
refrigerant. The designer,
however, should be cautious
with the quantity and size of fit-
Field-provided isolation ball Valves
It is acceptable to install field-supplied ball valves with Schrader
ports at the indoor unit. Full-port isolation ball valves with Schrader
ports (positioned between valve and the indoor unit) rated for use
with R410A refrigerant should be used on both the liquid and vapor
lines.
If valves are not installed and the indoor unit needs to be removed or
repaired, the entire system must be shut down and evacuated.
obstacles
When an obstacle, such as an I-beam or concrete T, is in the path
of the planned refrigerant pipe run, it is best practice to route the
pipe over the obstacle. If adequate space is not available to route
the insulated pipe over the obstacle, then route the pipe under the
obstacle. In either case, it is imperative the horizontal section of pipe
above or below the obstacle be a minimum of three (3) times greater
than the longest vertical rise (or fall) distance (Figure 15).
38 | reFrIGerAnT deSIGn
tings used, and must account for
the additional pressure losses in
equivalent pipe length calcula-
tion. The equivalent pipe length
of each elbow must be added to
each pipe segment. See Table
11 for equivalent lengths.
Due to our policy of continuous product innovation, some specifications may change without notification.
Table 11: Equivalent Piping Length for Piping Components
Component
1/4
Elbow (ft.)
0.5
Position valves with a minimum distance of three (3) to six (6) inches
of pipe on either side of the valve. Valves shall be easily accessible
for service. If necessary, install drywall access doors or removable
ceiling panels, and position the valves to face the access door or
ceiling panel opening. Mount valves with adequate space between
them to allow for placement of adequate pipe insulation around the
valves. Recommended best practice is to clearly label and docu-
ment locations of all service valves. The equivalent pipe length of
each ball valve must be added to each pipe segment.
Figure 15: Installing Piping Above and Below an obstacle
Above an obstacle.
Size (Inches)
3/8
1/2
5/8
3/4
0.6
0.7
0.8
1.2
3X
Minimum
Below an obstacle.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

La090hyvLan090hyvLau090hyvLa120hyvLan120hyvLau120hyv

Table of Contents