DIAGNOSTIC STATUS CODES
IT TRANSISTOR CONTROL
TRACTION
STATUS CODE
The field current exceeds the current limit
-66
of the field transistor.
MEMORY RECALL
YES
SYMPTOM
Control will not operate or is sluggish on
Circuits valid
start up. Line contactor opens.
for
Traction
POSSIBLE CAUSES
Controller
 Shorted field F1 to F2
 F1 or F2 terminals shorted to battery
positive (B+)
Confirm that all inductive
loads/accessories are suppressed.
Motor armature or field shorted to
frame.
Defective control.
Replace controller unit.
TRACTION
STATUS CODE
Capacitor (1C) voltage too high during
-76
pedal up regen braking.
MEMORY RECALL
YES
SYMPTOM
Line contactor opens and closes, then
Circuits valid
opens and can only close by opening
for
and closing the key switch.
Traction
Controller
POSSIBLE CAUSE
Batteries are overcharged.
 Regen current too high, cycle key
switch off then on.
Defective control.
Replace controller unit.
DESCRIPTION OF STATUS
CORRECTIVE ACTIONS
DESCRIPTION OF STATUS
CORRECTIVE ACTIONS
CAUSE OF STATUS INDICATION
This status code will be displayed when the field
transistor exceeds its current limit. The line
contactor will drop out and the key switch will have
to be recycled to restart the control.
TROUBLE-SHOOTING DIAGRAM
+72V
+72V
+72V
L
P1
P17
P2
P12
P3
P13
P22
72V
72V
72V
NEG
NEG
NEG
CAUSE OF STATUS INDICATION
This status code will be displayed when the voltage at
1C exceeds 96 volts during the regenerative braking
cycle.
TROUBLE-SHOOTING DIAGRAM
LINE
FU1
+
72 VDC
POS
A1
F1
-
POWER CONNECTIONS
NEG
A2
F2
Page 32
+72V
+72V
+72V +72V
P6
P4
P5
P10
P21
P9 P7
P8
P15 P14 P16
P23
P20
RS232
ACC POT
TACHOMETER
+72V
+72V
L
P1
P17
P2
P12
72V
NEG