Drainpipe and drain hose installation

AA
1 Push the supplied drain hose as far as possible over the drain socket.
2 Tighten the metal clamp as shown in the picture.
3 Wrap the supplied large sealing pad over the metal clamp and drain hose to insulate and fix it with clamps.
4 Insulate the complete drain piping inside the building (field supply).
If the drain hose cannot be sufficiently set on a slope, fit the hose with drain raising piping (field supply).
5 Push the drain hose up to insulation when connecting the drain hose to drain socket.
Metal clamp
Drain socket
Drain hose
Insulation drain
Check that the indoor unit is level with the ceiling by using the leveler.
CAUTION
Install air ventilation to drain condensate water smoothly.
Air ventilation
Do not give the hose and upward gradient after the
connection port. This will cause water to flow backwards
when the unit is stopped, resulting in water leaks.
• I f a concentrated drain pipe is installed, refer to the figure below.
NOTE
24 English
Drain piping
A-A'
Ceiling
Under gradient
Ceiling
Air ventilation
Tighten the provided metal clamp to
make sure that fifteen holes are able to
be seen at least.
If it is necessary to increase the height of the drainpipe,
install the drainpipe straightly within 300 mm from the
drain hose port. If it is raised higher than 550 mm, there
can be water leaks.
300mm or less
Band joint
Drain hose
Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as close
to the unit as possible.
Support pieces
1/100 or more
20mm or more
1/100 or more
Ceiling
1~1.5m
Ceiling
Concentrated drain pipe