Installation Options with Racks and Cabinets

Statement 1030—Equipment Installation
Warning
Only trained and qualified personnel should be allowed to install, replace, or service this equipment.

Installation Options with Racks and Cabinets

You can install the switch in the following types of racks using the rack-mount kit shipped with the switch:
• Open EIA rack
• Perforated EIA cabinet
The rack or cabinet that you use must meet the requirements listed in
Racks, on page
The rack-mount kit enables you to install the switch into racks of varying depths. You can use the rack-mount
kit parts to position the switch with easy access to either the port connections end of the chassis or the end of
the chassis with the fan and power supply modules. For instructions on how to install the rack-mount kit, see
the
Installing the Switch, on page

Airflow Considerations

The switch comes with fan and power supply modules that have either port-side intake or port-side exhaust
airflow for cooling the switch. If you are positioning the port end of the switch in a cold aisle, make sure that
the switch has port-side intake fan modules with burgundy coloring. If you are positioning the fan and power
supply modules in a cold aisle, make sure that the switch has port-side exhaust fan modules with blue colorings.
All fan modules must have the same direction of airflow.

Installation Guidelines

When installing the switch, follow these guidelines:
• Record equipment and installation information in the forms presented in
• Ensure that there is adequate clearance space around the switch to allow for servicing the switch and
• Ensure that you are positioning the switch in a rack so that it takes in cold air from the cold aisle and
• Ensure that the chassis can be adequately grounded. If the switch is not mounted in a grounded rack,
• Ensure that the site power meets the power requirements for the switch. If available, you can use an
Cisco Nexus 93108TC-FX ACI Mode Hardware Installation Guide
14
43.
as you install and configure the switch.
for adequate airflow.
exhausts air to the hot aisle. If there is blue coloring on the fan modules, the switch is configured for
port-side exhaust airflow and you must position the module side of the switch in a cold aisle. If there is
burgundy coloring on the fan modules, the switch is configured for port-side intake airflow and you
must position the port side of the switch in a cold aisle.
we recommend connecting both the system ground on the chassis directly to an earth ground.
uninterruptible power supply (UPS) to protect against power failures.
16.
Installing the Switch Chassis
General Requirements for Cabinets and
Chassis and Module Information