SMA SUNNY BOY 3800TL-US Installation Manual page 67

Hide thumbs Also See for SUNNY BOY 3800TL-US:
Table of Contents

Advertisement

SMA America, LLC
Event number
7105
7106
7110
7201 to 7202
7303
7305
Installation Manual
Display message
Param. setting failed
Update file defect.
No update file found
Data stor. not poss.
Update main CPU
failed
Update RS485I
module failed
Cause and corrective measures
Parameters cannot be set via the SD card. The
inverter continues feeding power into the grid.
Corrective measures:
• Check the parameters for valid values.
• Ensure change rights via SMA Grid Guard
code.
The update file is defective. The update failed.
The inverter continues feeding power into the
grid.
Corrective measures:
• Re-format the SD card.
• Re-save the files to the SD card.
No new update file was found on the SD card.
The update failed. The inverter continues feeding
power into the grid.
Corrective measures:
• Copy the update file into the SD card
drive:\UPDATE directory.
Internal device fault, the inverter continues
feeding power into the grid.
Corrective measures:
• If this error occurs frequently, contact the
SMA Service Line.
Internal device fault. The inverter continues
feeding power into the grid. In very rare cases,
the firmware is damaged and the inverter
interrupts the feed-in.
Corrective measures:
• Contact the SMA Service Line.
Internal device fault, the inverter continues
feeding power into the grid.
Corrective measures:
• Re-try update.
• If this error occurs again, contact the
SMA Service Line.
SB3-5TLUS22-IA-en-16
11  Troubleshooting
67