Mitsubishi Electric PAC-IF012B Technical Manual page 7

Air to water (atw) heat pump, interface (i/f) and flow temp. controller (ftc)
Table of Contents

Advertisement

(2) PUHZ-RP • VHA3/YHA3(2)
Outdoor unit
Model name
Power supply
(Phase, Voltage, Frequency)
Breaker size
Nominal water fl ow
Capacity
Heating
COP
(A2/W35)
Power input
Capacity
Heating
COP
(A7/W35)
Power input
Capacity
Heating
COP
(A7/W45)
Power input
Outdoor unit
Model name
Power supply
(Phase, Voltage, Frequency)
Breaker size
Nominal water fl ow
Capacity
Heating
COP
(A2/W35)
Power input
Capacity
Heating
COP
(A7/W35)
Power input
Capacity
Heating
COP
(A7/W45)
Power input
Guaranteed operating range (Outdoor)
Heating
:
Cooling
:
PUHZ-RP60VHA3#1
1[, 230V, 50Hz
A
25
L/min
20.1
kW
6.80
2.94
kW
2.31
kW
7.00
4.29
kW
1.63
kW
7.00
3.27
kW
2.14
PUHZ-RP71VHA3#1
1[, 230V, 50Hz
A
25
L/min
22.9
kW
7.50
2.92
kW
2.57
kW
8.00
4.21
kW
1.90
kW
8.00
3.20
kW
2.50
-11 ~ +35
-5 ~ +46
7
Plate heat exchanger
ALFA LAVAL
ACH50
A: 50 mm
Ref.IN
B: 466 mm
(Heating)
W:112 mm
H: 526 mm
D: 82 mm
Ref.OUT
30 plates
(Heating)
Refrigerant pipng length from outdoor unit to
heat exchanger (Water HEX): 5m
Maximum outlet water temperature
65
60
55
50
45
-10
-5
Ambient temperature [°C]
The performance might be decreased by the refrigerant
pipng length, insulation of refrigerant pipng and
heat exchanger (Water HEX).
w
Water OUT
B
H
A
Water IN
D
0
5
10

Advertisement