Mitsubishi Electric CRHV-P600YA-HPB Service Handbook page 35

Hot water heat pump
Table of Contents

Advertisement

[ II Restrictions ]
* Connect the heat source piping in reverse if the inlet temperature of heat source fluid is 27 °C or more.
(heat source fluid inlet is lower side, outlet is upper side) Install the attached label as shown below if the heat source fluid is
connected in reverse.
HWE1312A
INLET
Brine quality management
ethyleneglycol 35wt%.
To protect the heat exchanger from freezing,use the
Always use organic brine for this unit, and
maintain brine's freezing temperature below -18°C.
Water quality management
(Including water used for brine.)
To protect the heat exchanger from corrosion, the makeup
water and the circulating water need to meet the Water Quality
Standards below.
Makeup Water/Circulating Water Quality Standards
<Quoted from the Water Quality Standards(JRA GL-02-1994)>
Standard value
Circulating water
Circulating water
Item
Makeup
[above 20°C,
[above 60°C,
water
60°C or below]
90°C or below]
pH (25°C)
7.0~8.0
7.0~8.0
7.0~8.0
Electrical conductivity (mS/m)(25°C)
30 or less
30 or less
30 or less
Chloride ion(mgCl-/l)
Sulfate ion (mgSO
-/l)
30 or less
30 or less
50 or less
50 or less
30 or less
30 or less
Acid consumption (pH4.8)(mgCaCO
42
3
/l)
50 or less
50 or less
50 or less
Total hardness (mgCaCO
3
/l)
70 or less
70 or less
70 or less
Calcium hardness (mgCaCO
Ionic silica (mgSiO
/l)
3
/l)
30 or less
50 or less
50 or less
30 or less
50 or less
30 or less
Iron (mgFe/l)
2
0.3 or less
1.0 or less
1.0 or less
Copper (mgCu/l)
-/l)
0.1 or less
1.0 or less
1.0 or less
Ammonium ion (mgNH
Sulfide ion (mgS
2
/l)
Not to be detected
0.1 or less
Not to be detected
0.3 or less
Not to be detected
0.1 or less
Residual chlorine (mgCl/l)
4+
0.3 or less
0.25 or less
0.1 or less
Free carbon dioxide(mgCO
2
/l)
4.0 or less
0.4 or less
0.4 or less
Stability index
Installing the strainer (inlet side)
To prevent clogging the heat exchanger,install a strainer
at the heat exchanger inlet.(16-20 mesh)
OUTLET
KC79M182H01
Brine inlet/outlet
- 28 -
Accessory label (OUTLET)
OUTLET
Brine quality management
To protect the heat exchanger from freezing,use the
ethyleneglycol 35wt%.
Always use organic brine for this unit, and
maintain brine's freezing temperature below -18°C.
Water quality management
(Including water used for brine.)
To protect the heat exchanger from corrosion, the makeup
water and the circulating water need to meet the Water Quality
Standards below.
Makeup Water/Circulating Water Quality Standards
<Quoted from the Water Quality Standards(JRA GL-02-1994)>
Standard value
Circulating water
Circulating water
Item
Makeup
[above 20°C,
[above 60°C,
water
60°C or below]
90°C or below]
pH (25°C)
7.0~8.0
7.0~8.0
7.0~8.0
Electrical conductivity (mS/m)(25°C)
30 or less
30 or less
30 or less
Chloride ion(mgCl - /l)
30 or less
50 or less
30 or less
- /l)
Sulfate ion (mgSO
2
30 or less
50 or less
30 or less
4
Acid consumption (pH4.8)(mgCaCO
/l)
50 or less
50 or less
50 or less
3
Total hardness (mgCaCO
/l)
70 or less
70 or less
70 or less
3
Calcium hardness (mgCaCO
/l)
50 or less
50 or less
50 or less
3
Ionic silica (mgSiO
/l)
30 or less
30 or less
30 or less
2
Iron (mgFe/l)
0.3 or less
1.0 or less
1.0 or less
Copper (mgCu/l)
0.1 or less
1.0 or less
1.0 or less
- /l)
Sulfide ion (mgS
2
Not to be detected
Not to be detected
Not to be detected
Ammonium ion (mgNH
+
/l)
0.1 or less
0.3 or less
0.1 or less
4
Residual chlorine (mgCl/l)
0.3 or less
0.25 or less
0.1 or less
Free carbon dioxide(mgCO
/l)
4.0 or less
0.4 or less
0.4 or less
2
Stability index
Installing the strainer (inlet side)
To prevent clogging the heat exchanger,install a strainer
at the heat exchanger inlet.(16-20 mesh)
INLET
KC79M182H01
Accessory label (INLET)
GB

Advertisement

Table of Contents
loading