8.5.12. Hot Start Control
• Hot Start Control is to prevent cool air discharge into the room when heating operation start.
• When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
• Hot start is completed when indoor heat exchanger rises to 39°C or operation over 4 minutes.
8.5.13. Anti Cold Draft Control
• This operation is to prevent the Cold Draft during Heating mode operation.
• The operation will start when compressor OFF (Thermo OFF) during Heating operation.
• For the first 30 sec. from compressor OFF (Thermo OFF), Indoor fan speed will operate accordingly to the Indoor heat
exchanger temperature as shown below:
• After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run at SSLo speed only.
• Anti Cold Draft Control will stop when:
− Intake temperature < set temperature. (Time Delay Safety Control 4 minutes waiting is valid)
− 30 Minutes Time Save Control activates.