If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases, resistance to
the flow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective.
Always choose the shortest path and follow the recommendations as tabulated below:
Heat Pump Model
Model
Min. Allowable Length (L), m
Max. Allowable Length (L), m
Max. Allowable Elevation (E), m
Gas Pipe Size, mm/(in)
Liquid Pipe Size, mm/(in)
Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
*
Remark: The refrigerant pre-charged in the outdoor unit is for piping length up to 7.5m.

REFRIGERANT PIPING

Indoor unit
Outdoor Unit
Indoor (ATYN)
Outdoor (ARYN)
www.mrklimat.ru
L
20J
25J
20C
25C
12
12
5
5
9.52
9.52
(3/8")
(3/8")
6.35
6.35
(1/4")
(1/4")
1-9
Тел.: 8-800-5555-710
E
35J
50J
35C
50C
3
12
20
5
15
12.70
12.70
(1/2")
(1/2")
6.35
6.35
(1/4")
(1/4")
60J
60C
20
15
15.88
(5/8")
6.35
(1/4")