2.4.4.9. P0 Malfunction
Malfunction conditions
Possible causes
First, test the resistance between every two ports of U, V, the W of the IPM and P, N. If any of the results is 0
or close to 0, the IPM is defective. If not, follow the following procedure:
Electrical Control System
When the voltage signal te IPM sends to compressor drive
chip is not normal, the LED displays "P0" and the unit turns off.
Wiring mistakes
●
Faulty IPM board
●
Faulty outdoor fan assemby
●
Compressor malfunction
●
Faulty outdoor PCB
●
Troubleshooting