Indoor Unit Fixing; Drainage - Toshiba MMK-AP0054MHP-E Installation Manual

Indoor unit high-wall type
Table of Contents

Advertisement

High-Wall Type
SMMS High-Wall Type
7.

Indoor Unit Fixing

1
Pass the pipe through the hole in the wall,
and hook the indoor unit on the installation
plate at the upper hooks.
2
Swing the indoor unit to right and left to
confirm that it is firmly hooked up on the
installation plate.
3
While pressing the indoor unit onto the wall,
hook it at the lower part on the installation
plate. Pull the indoor unit toward you to
confirm that it is firmly hooked up on the
installation plate.
Hook here
1
Installation plate
2
Hook
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while
pushing its bottom up at the specified parts.
Push
Press
(unhook)
Push
– 18 –
8.

Drainage

1
Run the drain hose sloped downwards.
NOTE
• Hole should be made at a slight downward slant
on the outdoor side.
2
Put water in the drain pan and confirm that
the water is drained out of doors.
3
Before connecting extension drain hose,
insulate the connecting part of extension
drain hose with shield pipe.
Do not rise the drain hose.
50 mm
or more
Do not put the
drain hose end
into water.
Shield pipe
Inside the
Drain hose
room
CAUTION
Arrange the drain pipe for proper drainage from
the unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to
drain water collected from dew, which forms on the
back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and other
parts at a height above the drain guide.
Space for pipes
Installation Manual
Do not form the drain hose
into a wavy shape.
Do not put the
drain hose end
in the drainage
ditch.
Extension drain hose
Wall
Drain guide
18-EN
EN

Advertisement

Table of Contents
loading

Table of Contents