How To Install The Indoor Unit; Slim Low Static Ducted Type (Type M1); Required Minimum Space For Installation And Service - Panasonic S-15MM1E5A Installation Instructions Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1

3. HOW TO INSTALL THE INDOOR UNIT

■ Slim Low Static Ducted Type (Type M1)

3-1. Required Minimum Space for Installation and
Service
● This air conditioner is usually installed above the ceiling so
that the indoor unit and ducts are not visible. Only the air
intake and air outlet ports are visible from below.
● The minimum space for installation and service is shown in
the diagram. (Fig. 3-1)
● *H dimension means the minimum height of the unit.
● Select the *H dimension such that a downward slope of at
least 1/100 is ensured as indicated in "3-6. Installing the
Drain Pipe".
● The diagram shows the detailed dimensions of the indoor
unit. (Fig. 3-2)
(Flange for air outlet duct)
(Suspension bolt pitch)
6
29
692
96
66
640 (160x4)
26
5-ø3.1(Hole)
4
750
37
150
824
9
680
824(Suspension bolt pitch)
Min. 200
or more
Flange for air
outlet duct
Min. 100 mm or more for bottom air intake
1 Refrigerant tubing joint (narrow tube)
2 Refrigerant tubing joint (wide tube)
3 Upper and bottom drain port (O.D.26 mm)
4 Suspension lug
5 Power supply outlet (ø17)
6 Flange for air outlet duct
7 Cover plate
8 Electrical component box
9 Filter
Inter-unit control wiring and control wiring for
0
group control outlet (ø15)
! Remote control wiring outlet (ø15)
Water inlet
Inspection access
(450x450)
(Field supply)
10-ø3.1(Hole)
5
10
14
11
132
220
23
* Filter Uninstalled
7
Electrical
component box
Inspection
access
450x450
Refrigerant tubing
Min. 650 or more
Min. 20 or more
Min. 20 or more
Ceiling
Unit : mm
2-ø3.1(Hole)
28
30
84
81
7
1
33
2
153
3
8
150
200
14
220
132
704
23
Unit: mm
Fig. 3-1
Fig. 3-2