olympia electronics GRL-38/90/M Manual page 3

Self testing non maintained emergency luminaires

Advertisement

INSTALLATION PROCEDURE (For wall mounting only)
Mounting holes
Fig. 1
Cover
retaining
screws
LAMP FAULT
BATT. FAULT
indicator
TEST
button
Fig. 3
1. Install the included mounting accessories to hook the device from the mounting holes (Fig.1).
2. Unfasten the 4 mounting screws to remove the front plastic cover (Fig.1).
3. Make sure that the battery's cables are connected to the respective poles. Black cable to (-) pole
and red cable to (+) pole (Fig. 2).
4. Install the included cable gland or the rubber o-ring. Pass through the mains cable and stabilize it
by fastening the cable gland. Connect the wires to the terminal blocks L for live wire and Ν for
neutral (Fig. 2).
5. If you use a module, open a hole in one of the two sides of the luminaire (Fig.3). Install the cable
grommet and pass the 2 signal cables on the C,NO terminal (Fig. 4), minding the correct
polarity. Depending on the module that will be used, the cables, have different names. In C,
signal +L, A are also connected, while signals -L, B in the terminal NO (Fig.4).
6. Refit with care the front plastic cover, by fastening the 4 mounting screws (tightening torque
1N*m).
WARNING!!
After the installation has finished, charge the batteries for at least 24 hours so as to obtain the
rated autonomy duration.