Auxiliary Power Operation; Simultaneous Welding And Auxiliary Power Loads - Lincoln Electric Vantage LE500X Operator's Manual

For use with machines having code numbers: 12883, 12891, 13195, 13196
Table of Contents

Advertisement

VANTAGE
441X/LE500X
®

AUXILIARY POWER OPERATION

Start the engine and set the RUN / STOP / IDLE switch to the
desired operating mode. Full power is available regardless of the
welding control settings, if no welding current is being drawn.
The auxiliary power of the Vantage
two 20 amp 120 VAC (5-20R) duplex receptacles with GFCI
protection, one 50 amp 120/240 VAC single phase (14-50R)
receptacle and one 50 amp 240 VAC three phase (15-50R)
receptacle.
The auxiliary power capacity is 11,000 watts of 60 Hz, single
phase power or 17,000 watts of 60 Hz, three phase power. The
auxiliary power capacity rating in watts is equivalent to volt-
amperes at unity power factor. The maximum permissible current
of the 240 VAC output is 50 A. The 240 VAC single phase output
can be split to provide two separate 120 VAC outputs with a
maximum permissible current of 50 A per output to two separate
120 VAC branch circuits. Output voltage is within ± 10% at all
loads up to rated capacity.
NOTE: The two 120V GFCI receptacles and the two 120V circuits
of the 120/240V receptacle are connected to different phases
and cannot be paralleled.
The auxiliary power receptacles should only be used with three
wire grounded type plugs or approved double insulated tools with
two wire plugs.
The current rating of any plug used with the system must be at
least equal to the current capacity of the associated receptacle.
TABLE B.5 VANTAGE® 441X/LE500X PERKINS SIMULTANEOUS WELDING AND POWER LOADS
WELD
AMPS
WATTS
0
11,000
100
11,000
PLUS
200
300
400
up to 500
Current
Voltage
Load
(Amps)
(Volts)
(Watts)
15
120
1800
15
240
3600
20
120
2400
20
240
4800
25
240
6000
30
240
7200
38
240
9000
50
240
12000
441X/LE500X consists of
®
1 PHASE
AMPS
46
46
OR
8000
33
4700
20
1700
7
0
0
TABLE B.6 VANTAGE® 441X/LE500X PERKINS
EXTENSION CORD LENGTH RECOMMENDATIONS
Maximum Allowable Cord Length in ft. (m) for Conductor Size
14 AWG
12 AWG
30
(9)
40
(12)
60
(18)
75
(23)
30
(9)
60
(18)
Conductor size is based on maximum 2.0% voltage drop.
SIMULTANEOUS WELDING AND AUXILIARY POWER
LOADS
The auxiliary power capacity previously stated is maintained
without any welding load. If a welding load is present, the
available auxiliary power will decrease.
Simultaneous welding and power loads are specified in Table
B.5. The permissible currents shown assume that current is
being drawn from either the 120 VAC or 240 VAC supply (not both
at the same time).
3 PHASE
WATTS
AMPS
17,000
41
15,400
37
OR
13,000
31
9400
23
3400
8
0
0
10 AWG
8 AWG
75
(23)
125
150
(46)
225
50
(15)
88
100
(30)
175
90
(27)
150
75
(23)
120
100
B-15
BOTH 1 AND 3 PHASE
WATTS
AMPS
11,000
------
11,000
------
8000
------
4700
------
1700
------
0
6 AWG
(38)
175
(53)
300
(69)
350
(107)
600
(27)
138
(42)
225
(53)
275
(84)
450
(46)
225
(69)
250
(37)
175
(53)
300
(30)
150
(46)
250
125
(38)
200
OPERATION
0
4 AWG
(91)
(183)
(69)
(137)
(76)
(91)
(76)
(61)