E51C2A, E51C3A Installation Guide
Modbus Point Map (cont.)
R/W NV Format
• 287/288 R
Float
• 289/290 R
Float
• 291/292 R
Float
• 293/294 R
Float
• 295/296 R
Float
• 297/298 R
Float
• 299/300 R
NV
Float
• 301/302 R
NV
Float
• 303/304 R
NV
Float
• 305/306 R
NV
Float
• 307/308 R
NV
Float
• 309/310 R
NV
Float
• 311/312 R
Float
• 313/314 R
Float
• 315/316 R
Float
• 317/318 R
Float
• 319/320 R
Float
• 321/322 R
Float
• 323/324 R
Float
• 325/326 R
Float
• 327/328 R
Float
• 329/330 R
Float
• 331/332 R
Float
• 333/334 R
Float
• 335/336 R
Float
• 337/338 R
Float
• 339/340 R
Float
• 341/342 R
Float
• 343/344 R
Float
• 345/346 R
Float
• 347/348 R
Float
• 349/350 R
Float
• 351/352 R
Float
• 353/354 R
Float
• 355/356 R
Float
• 357/358 R
Float
• 359/360 R
Float
• 361/362 R
Float
• 363/364 R
Float
ZL0122-0D
Page 28 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Units Scale
Range
Volt
Voltage, L-N (V), average of active phases
Amp
Current, average of active phases
Hz
45.0-65.0
Frequency
kW
Total Real Power Present Demand
kVAR
Total Reactive Power Present Demand
kVA
Total Apparent Power Present Demand
kW
Total Real Power Max. Demand
kVAR
Total Reactive Power Max. Demand
kVA
Total Apparent Power Max. Demand
kW
Total Real Power Max. Demand
kVAR
Total Reactive Power Max. Demand
kVA
Total Apparent Power Max. Demand
Reserved, reports QNAN (0x7FC00000)
1
0-4294967040
Pulse Counter 1 (Import Real Energy)
1
0-4294967040
Pulse Counter 2 (Export Reactive Energy
Floating Point Data: Per Phase
kWh
Accumulated Real Energy, Phase A
kWh
Accumulated Real Energy, Phase B
kWh
Accumulated Real Energy, Phase C
kWh
Accumulated Real Energy, Phase A
kWh
Accumulated Real Energy, Phase B
kWh
Accumulated Real Energy, Phase C
kVARh
Accumulated Q1 Reactive Energy, Phase A
kVARh
Accumulated Q1 Reactive Energy, Phase B
kVARh
Accumulated Q1 Reactive Energy, Phase C
kVARh
Accumulated Q2 Reactive Energy, Phase A
kVARh
Accumulated Q2 Reactive Energy, Phase B
kVARh
Accumulated Q2 Reactive Energy, Phase C
kVARh
Accumulated Q3 Reactive Energy, Phase A
kVARh
Accumulated Q3 Reactive Energy, Phase B
kVARh
Accumulated Q3 Reactive Energy, Phase C
kVARh
Accumulated Q4 Reactive Energy, Phase A
kVARh
Accumulated Q4 Reactive Energy, Phase B
kVARh
Accumulated Q4 Reactive Energy, Phase C
kVAh
Accumulated Apparent Energy, Phase A
kVAh
Accumulated Apparent Energy, Phase B
kVAh
Accumulated Apparent Energy, Phase C
kVAh
Accumulated Apparent Energy, Phase A
kVAh
Accumulated Apparent Energy, Phase B
kVAh
Accumulated Apparent Energy, Phase C
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Description
Import
Export
Contact closure counters. Valid for both pulse
inputs and outputs. E51CxA counts are shown
in (). See register 144 for the weight of each
pulse output count. These values are derived
from the 32 bit integer counter and roll over
to 0 when the integer counters do. Inputs are
user defined.
Import
Accumulated Real Energy (Ph)
Export
Quadrant 1
Import
Quadrant 2
Quadrant 3
Export
Quadrant 4
Import
Accumulated Apparent Energy (Sh)
Export
TM
Accumulated
Reactive Energy
(Qh)
0818