E51C2A, E51C3A Installation Guide
Solid-State
Pulse Output
User Interface (UI)
Menu Abbreviations
Defined
ZL0122-0D
Page 11 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
The meter has one normally open (N.O.) KZ Form
A output and one normally closed (N.C.) KY
solid-state output. One is dedicated to import
energy (Wh), and the other to Alarm.
The relay used for the Phase Loss contact is N.C.,
with closure indicating the presence of an alarm;
either loss of phase if the meter is powered, or
loss of power if the meter is not. The contacts are
open when the meter is powered and no phase
loss alarm conditions are present.
The solid state pulse outputs are rated for 30
Vac/dc nom.
Maximum load current is 100 mA at 25 °C.
Derate 0.56 mA per °C above 25 °C.
See the Setup section for configuration
information.
The user can set the display mode to either IEC or IEEE notation in the SETUP menu.
Main Menu
IEC
IEEE
D
D
Demand
MAX
M
Maximum Demand
P
W
Present Real Power
Q
VAR
Present Reactive Power
S
VA
Present Apparent Power
A
A
Amps
UAB, UBC, UAC
VAB, VBC, VAC
Voltage Line to Line
V
VLN
Voltage Line to Neutral
PF
PF
Power Factor
U
VLL
Voltage Line to Line
HZ
HZ
Frequency
KSh
KVAh
Accumulated Apparent
Energy
KQh
KVARh
Accumulated Reactive
Energy
KPh
KWh
Accumulated Real Energy
PLOSS
PLOSS
Phase Loss
LOWPF
LOWPF
Low Power Factor Error
F ERR
F ERR
Frequency Error
I OVR
I OVR
Over Current
V OVR
V OVR
Over Voltage
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
+
Alarm
Energy
Output
* The over-current protective device must be rated for the short circuit current at the
connection point.
** All pulse outputs and communication circuits are only intended to be connected to
non-hazardous circuits (SELV or Class 2). Do not connect to hazardous voltages.
Description
IEC
PULSE
_PHASE
ALERT
INFO
MODEL
OS
RS
SN
RESET
PASWD
ENERG
DEMND
PULS_
Q_
n
Over-Current Protective
Device* (not supplied)
≤ 100 mA
Power Source**
~
=
≤ 100 mA
~
=
S
Main Menu
IEEE
Description
PULSE
kWh Pulse Output Overrun
(configuration error)
_PHASE
Summary Data for 1, 2, or 3
active phases
ALERT
Diagnostic Alert Status
INFO
Unit Information
MODEL
Model Number
OS
Operating System
RS
Reset System
SN
Serial Number
RESET
Reset Data
PASWD
Enter Reset or Setup
Password
ENERG
Reset Energy Accumulators
DEMND
Reset Demand Maximums
Import
Export
PULS_
Pulse Counter (if equipped)
Q_
Quadrant 1-4 per IEEE 1459
n
Net
TM
3-30 Vdc
6-30 Vac
Power Source**
3-30 Vdc
6-30 Vac
0818