Specifications (cont.)
SunSpec Alliance
Interoperability
Specification
Compliance
ZL0122-0D
Page 2 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
AC
DC*
Ride-through Time
Alarm Contacts
Real Energy Pulse Contacts
RS-485 Port
Weight
IP Degree of Protection
(IEC 60529)
Display Characteristics
Terminal Block Screw Torque
Terminal Block Wire Size
Rail
Operating Temperature Range
Storage Temperature Range
Humidity Range
Altitude of Operation
Mounting Location
US and Canada
Europe (CE)
Dielectric Withstand
Conducted and Radiated
Emissions
Conducted and Radiated
Immunity
US and Canada (cULus)
* External DC current limiting is required, see fuse recommendations.
This meter implements the draft SunSpec 1.0 common elements starting at base 1 address 40001, and the proposed SunSpec 1.1
meter model at 40070 (these addresses are not in Modicon notation). See www.veris.com or www.sunspec.org for copies of these
specifications.
The SunSpec Alliance logo is a trademark or registered trademark of the SunSpec Alliance.
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
CONTROL POWER
5 VA max.; 90 V min.;
UL Maximums: 600 V
(347 V
); CE Maximum: 300 V
L-L
L-N
3W max.; UL and CE: 125 to 300 Vdc
100 msec at 120 Vac
OUTPUT
N.C., static output (30 Vac/dc, 100mA max. @ 25 °C,
derate 0.56 mA per °C above 25 °C)
N.O., static output (30 Vac/dc, 100 mA max. @ 25 °C,
derate 0.56 mA per °C above 25 °C)
2-wire, 1200 to 38400 baud, Modbus RTU
MECHANICAL CHARACTERISTICS
0.62 lb (0.28 kg)
IP40 front display; IP20 meter
Back-lit blue LCD
0.37 to 0.44 ft-lb (0.5 to 0.6 N·m)
24 to 14 AWG (0.13 to 2.08 mm
)
2
T35 (35mm) DIN Rail per EN 50022
OPERATING CONDITIONS
-30 to 70 °C (22 to 158 °F)
-40 to 85 °C (-40 to 185 °F)
<95% RH non-condensing
3000 m
Not suitable for wet locations. For indoor use only.
COMPLIANCE INFORMATION
CAT III, Pollution Degree 2;
for distribution systems up to 347 V
/600 Vac
L-N
IEC/EN 61010-1;
CAT III, Pollution Degree 2;
for distribution systems up to 300 V
L-N
Per UL 508, IEC/EN 61010-1
FCC part 15 Class B, EN 55011/EN 61000 Class B
(residential and light industrial)
EN 61000 Class A
(heavy industrial)
UL 508 (open type device) / CSA 22.2 No. 14-05
L-N
L-L
TM
0818