E51C2A, E51C3A Installation Guide
Modbus Point Map (cont.)
R/W NV Format
• 079
R
NV
ULong
• 080
• 081
R
NV
ULong
• 082
• 083
R
NV
ULong
• 084
• 085
R
NV
ULong
• 086
• 087
R
NV
ULong
• 088
• 089
R
NV
ULong
• 090
• 091
R
SInt
• 092
R
SInt
• 093
R
SInt
• 094
R
SInt
• 095
R
SInt
• 096
R
SInt
• 097
R
UInt
• 098
R
UInt
• 099
R
UInt
• 100
R
SInt
• 101
R
SInt
• 102
R
SInt
• 103
R
UInt
• 104
R
UInt
• 105
R
UInt
• 106
R
UInt
• 107
R
UInt
• 108
R
UInt
• 109
R
UInt
• 110
R
UInt
• 111
R
UInt
• 112
R
UInt
ZL0122-0D
Page 22 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Units Scale
Range
Accumulated Apparent Energy,
kVAh
E
0 to 0xFFFFFFFF
Accumulated Apparent Energy,
kVAh
E
0 to 0xFFFFFFFF
Accumulated Apparent Energy,
kVAh
E
0 to 0xFFFFFFFF
Accumulated Apparent Energy,
kVAh
E
0 to 0xFFFFFFFF
Accumulated Apparent Energy,
kVAh
E
0 to 0xFFFFFFFF
Accumulated Apparent Energy,
kVAh
E
0 to 0xFFFFFFFF
kW
W
-32767 to +32767 Real Power (P), Phase A
kW
W
-32767 to +32767 Real Power (P), Phase B
kW
W
-32767 to +32767 Real Power (P), Phase C
kVAR
W
-32767 to +32767 Reactive Power (Q), Phase A
kVAR
W
-32767 to +32767 Reactive Power (Q), Phase B
kVAR
W
-32767 to +32767 Reactive Power (Q), Phase C
kVA
W
0 to 32767
Apparent Power (S), Phase A
kVA
W
0 to 32767
Apparent Power (S), Phase B
kVA
W
0 to 32767
Apparent Power (S), Phase C
Ratio
0.0001 -10000 to +10000 Power Factor (PF), Phase A
Ratio
0.0001 -10000 to +10000 Power Factor (PF), Phase B
Ratio
0.0001 -10000 to +10000 Power Factor (PF), Phase C
Volt
V
0 to 32767
Voltage (U), Phase A-B
Volt
V
0 to 32767
Voltage (U), Phase B-C
Volt
V
0 to 32767
Voltage (U), Phase A-C
Volt
V
0 to 32767
Voltage (V), Phase A-N
Volt
V
0 to 32767
Voltage (V), Phase B-N
Volt
V
0 to 32767
Voltage (V), Phase C-N
Amp
I
0 to 32767
Current, Phase A
Amp
I
0 to 32767
Current, Phase B
Amp
I
0 to 32767
Current, Phase C
Reserved, Returns 0x8000 (QNAN)
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
MSR
Phase A
LSR
MSR
Phase B
LSR
MSR
Phase C
LSR
MSR
Phase A
LSR
MSR
Phase B
LSR
MSR
Phase C
LSR
Description
Import
Export
Real Power (P)
Reactive Power (Q)
Apparent Power (S)
Power Factor (PF)
Line to Line Voltage (U)
Line to Neutral Voltage (V)
Current
TM
Accumulated
Apparent Energy
(Sh), Per Phase
0818

Advertisement

loading

This manual is also suitable for:

E51c3a