Veris Industries E51C2A Installation Manual page 16

Compact bi-directional power and energy meter for use only with e683 series rope cts

Advertisement

E51C2A, E51C3A Installation Guide
UI for Setup
(cont.)
To Setup p. 1 "S PWR"
Back
SPLOS
Phase
Loss
Back
SPULS
Pulse
Output
Back
SDMND
Demand
Back
S DIS
Display
Units
Back
SPASS
Setup
Passwords
To Setup page 1 "S COM"
ZL0122-0D
Page 16 of 34
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
VOLTS
IMBAL
--------
--------
0.10
0.25
Next
mS/P
Wh/P
--------
--------
--------
500
10000
250
1000
100
100
50
10
25
10
Next
INTRV
--------
6
SEC
5
--------
4
00900
3
2
Next
1
UNITS
--------
IEEE
IEC
Next
SETUP
RESET
--------
--------
00000
00000
Next
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Set Phase Loss:
VOLTS - Phase Loss Voltage: The fraction of the system
voltage below which Phase Loss Alarm is on. For system
types with neutral, the Line to Neutral voltage is also
calculated and tested. If the System Voltage is 600 and the
fraction is set to 0.10, then the Phase Loss threshold will be
60 volts.
IMBAL - Phase Loss Imbalance: The fractional difference
in Line to Line voltages above which Phase Loss Alarm is
on. For system types with neutral, the Line to Neutral
voltages are also tested. For system types 1+N (10) and 2
(11) , imbalance is not tested.
Set Pulse:
The System Type , CT size, PT Ratio, and System Voltage must
all be configured before setting the Pulse Energy. If any of these
parameters are changed, the meter will hunt for a new Pulse
Duration, but will not change the Pulse Energy. If it cannot find a
Max
solution, the meter will display the wrench, show "ConF" in the
PPS
ALARM -> PULSE screen, and enable Energy pulse output
configuration error bit in the Modbus Diagnostic Alert Bitmap (if
1
equipped).
2
Wh/P - Set Pulse Energy: In Watt Hours (& VAR Hours, if
5
present) per Pulse. When moving down to a smaller energy, the
10
meter will not allow the selection if it cannot find a pulse duration
20
that will allow the pulse output to keep up with Theoretical
50
Maximum System Power (see S_PWR screen). When moving
up to a larger energy, the meter will jump to the first value where
it can find a valid solution.
mS/P – Minimum Pulse Duration Time: This read only value
is set by the meter to the slowest duration (in mS per closure)
that will keep up with the Theoretical Maximum System Power.
The open time is greater than or equal to the closure time. The
maximum Pulses Per Second (PPS) is shown in yellow.
Set Demand Interval:
INTRV - The number of Sub-Intervals (1 to 6) in a Demand Interval.
Default is 1 (block demand).
SEC - Sub-Interval length in seconds. Default is 900 (15 minutes).
Set to 0 for external sync-to-comms (Modbus units only).
Set Display Units: +/- to switch between:
IEEE – VLL VLN W VAR VA Units.
IEC -
U
V
P
Set Passwords:
SETUP - The Password to enter the SETUP menu.
RESET - The Password to enter the RESET menu.
Q
S Units.