M-system R7L-YV2 Instruction Manual page 16

Dc voltage output module, 2 points (lonworks)
Table of Contents

Advertisement

■ FUNCTIONAL BLOCK: fbDIEX[0...7]
• Network Variables
Normal Mode
TYPE
NETWORK
{ Range }
VARIABLE
{ Default }
{SNVT_switch}
nvoDIEX1
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
{SNVT_switch}
nvoDIEX2
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
Combination Mode
TYPE
NETWORK
{ Range }
VARIABLE
{ Default }
{SNVT_switch}
nvoDIEX1
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
{SNVT_switch}
nvoDIEX2
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
• Configuration Properties
CONFIGURATION
NETWORK
PROPERTY
VARIABLE
SCPTdirection
----
SCPTinvrtOut
nvoDIEX1
SCPTinvrtOut
nvoDIEX2
EXPLANATIONS
Outputs X0, X2, X4, X6, X8, XA, XC, XE status of the extension module
Outputs X1, X3, X5, X7, X9, XB, XD, XF status of the extension module
EXPLANATIONS
TYPE
{ Range }
{ Default }
{SNVT_state}
{0 or 1}
{0,0,0,0,0,0,0,0,
0,0,0,0,0,0,0,0}
{SNVT_lev_disc}
{ST_OFF, ST_ON}
{ST_OFF}
{SNVT_lev_disc}
{ST_OFF, ST_ON}
{ST_OFF}
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
Contact input, nvoDIEX1 and nvoDIEX2 Reference Table
X0
X1
X2
X3
X4
X5
X6
X7
X8
X9
XA
XB
XC
XD
XE
XF
OFF
OFF
ON
OFF
100.0 1 (ON)
OFF
ON
ON
ON
100.0 1 (ON)
EXPLANATIONS
Bit 0, Bit 1: fbDIEX operating mode
0,0 : Normal mode
0,1 : Combination mode
Bit 2 through 15 : Invalid
Contact input logic is inverted at nvoDIEX1.
ST_OFF : OFF at open contact, ON at closed contact
ST_ON : ON at open contact, OFF at closed contact
Contact input logic is inverted at nvoDIEX2.
ST_OFF : OFF at open contact, ON at closed contact
ST_ON : ON at open contact, OFF at closed contact
R7L-YV2
nvoDIEX1
nvoDIEX2
0.0 0 (OFF)
Invalid
Invalid
0.0 0 (OFF)
0.0 0 (OFF)
100.0 1 (ON)
EM-7804-D Rev.5 P. 16 / 16