Drain pipe and drain installaton
AA
1. Unscrew the 4 tapped screws to remove the cover of the drain hose
connection port.
2. Insert the flexible hose to the drain hose port.
• Fix the flexible hose to the indoor unit wiht the supplied cable
clamp securely.
(Use the screwdriver to fix the flexible hose securely.)
3. Install the drain hose so that its length can be as short as possible. Internal diameter of the drain hose should be the
same or slightly bigger than the external diameter of the drain hose port.
Inner diameter of the drain hose
• Install the drain hose with a slope away from the unit to give adequate drainage of condensate.
• Fix the flexible hose to the PVC with the supplied cable tie securely.
4. Wrap the drain hose with the insulation drain as shown in figure and secure it.
36
RHF050KHEA_IB,IM_E_32885-3.indd 36
Cable clamp
32mm(Inner diameter)
Indoor
unit
Drain hose connection port
Cable-tie
Clamp
Insulation drain hose
Insulation cover drain
• Must fit tightly against
body without any gap.
No gap
2011-10-12 오후 5:30:35