Samsung Fresh Access AN035NSEDAV/AA Installation Manual

Light commercial models energy recovery ventilators
Table of Contents

Advertisement

Available languages

Available languages

Installation Manual
Light commercial models
Energy Recovery Ventilators
Your ventilation system should be installed in conformance with the appropriate provincial requirements or, in
the absence of such requirements, with the current edition of the National Building Code, and / or ASHRAE's
Samsung HVAC reserves the right to modify, at any time and without notice, any or all of its products features, designs,
components and specifications to maintain their technological leadership position.
Please visit our website www.SamsungHVAC.com for more detailed technical information.
MODELS: AN035NSEDAV/AA, AN075NSEDAV/AA, AN120NSEDAV/AA
"Good Engineering Practices".
SHA-FAERV-09212018
Source Rev Date: 2018-09-05

Advertisement

Table of Contents
loading

Summary of Contents for Samsung Fresh Access AN035NSEDAV/AA

  • Page 1 National Building Code, and / or ASHRAE’s “Good Engineering Practices”. Samsung HVAC reserves the right to modify, at any time and without notice, any or all of its products features, designs, SHA-FAERV-09212018 components and specifications to maintain their technological leadership position.
  • Page 2 Note Warning/ Information Technical Practical tip Important information note PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT Before installation, careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler, operating at a higher static.
  • Page 3: Table Of Contents

    Table of contents INSTALLATION Location..............4 Port Configuration.
  • Page 4: Installation

    Installation Location The ERV must be located in a conditioned space where it will be possible to conveniently service the unit. Typically the ERV would be located in the mechanical room, above a drop ceiling or an area close to the outside wall where the weatherhoods will be mounted. Attic installations are not normally recommended due to extreme temperatures, and difficulty in performing required service &...
  • Page 5: Port Configuration

    Port configuration The unit has access doors on the front and back. Also, the main control panel may be moved from front to back allowing for ducting layout. AN035NSEDAV/AA and AN075NSEDAV/AA WARM SIDE COLD SIDE WARM SIDE COLD SIDE Factory Setting. Unit may be easily reversed in field.
  • Page 6 Installing Drain Line Through normal operation and including defrost mode, the ERV may produce some condensation. This water should flow into a nearby drain, or be taken away by a condensate pump. The ERV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point.
  • Page 7: Airflow Balancing

    Installing ducts to / from inside To maximize airflow in the ductwork system, all ducts should be kept short and have as few bends or elbows as possible. Forty- five degree are preferred to 90o elbows. Use “Y” tees instead of mitered tee whenever possible. All duct joints must be fastened with screws or duct sealant and wrapped with a quality duct tape to prevent leakage.
  • Page 8: Installation Examples

    Installation examples Drawings are illustrations only and actual port locations and airflow directions may vary, consult unit spec sheets. It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended. The amount of air (CFM) that an ERV will deliver is directly related to the total external static pressure (E.S.P.) of the system.
  • Page 9: Partially Dedicated Systems (Indirect Connections)

    Installation examples (Cont'd) * Drawings are illustrations only and actual port locations and airflow directions may vary, consult unit spec sheets. It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended. The amount of air (CFM) that an ERV will deliver is directly related to the total external static pressure (E.S.P.) of the system.
  • Page 10: Modes Of Operation

    Modes of operation 1. Continuous / Ventilation Mode In this mode of operation both fans are operating and exchanging inside air for outside air. The energy recovery ventilator (ERV) will operate at the selected rate, either at low or medium speed, and switches to high speed when activated by an optional remote control. The "LOW (reduced)"...
  • Page 11 Setting low speed (AN120NSEDAV/AA) CAUTION MAKE SURE THE POWER TO THE UNIT IS DISCONNECTED BEFORE MAKING ANY CHANGES The ERV is shipped from the factory on low speed, intermittent operation can be obtained by toggling switch located on outside of cabinet. The voltage selection for low (reduced) speed of the unit is done via jumpers shown in the illustration below.
  • Page 12: Low Voltage Control System

    Low Voltage Control Systems * Please see instruction manuals for individual controls for proper wiring and set up of control systems. Wired Controller Wired control options can only be used individually CONTROLS FEATURES CONNECT TO ECO-Touch® • Our most complete, yet easy to use control system •...
  • Page 13: Maintenance

    Maintenance CAUTION MAKE SURE UNIT IS UNPLUGGED BEFORE ATTEMPTING ANY MAINTENANCE WORK The following components should also be inspected regularly and well maintained. The motor - The motors are factory balanced and lubricated for life. They require no maintenance. The unit - The inside of the unit should be wiped clean as needed. Outside hoods - The outside hoods need to be checked every season to make sure there are no leaves or insects blocking the airflow.
  • Page 14 Standard Furnace Interlock Wiring THERMOSTAT TERMINALS FOUR WIRE TWO WIRE heating only RV-CTRL 24VAC FURNACE 24-VOLT TERMINAL BLOCK COOLING SYSTEM WIRE Standard Furnace Interlock Wiring (w/Damper) THERMOSTAT TERMINALS FOUR WIRE TWO WIRE heating only RV-CTRL 24VAC FURNACE 24-VOLT TERMINAL BLOCK COOLING SYSTEM WIRE SHUTOFF...
  • Page 15 Alternate Furnace Interlock Wiring THERMOSTAT TERMINALS FOUR WIRE TWO WIRE heating only RV-CTRL 24VAC FURNACE 24-VOLT TERMINAL BLOCK COOLING SYSTEM WIRE Alternate Furnace Interlock Wiring (w/Damper) THERMOSTAT TERMINALS FOUR WIRE TWO WIRE heating only RV-CTRL 24VAC FURNACE 24-VOLT TERMINAL BLOCK COOLING SYSTEM WIRE SHUTOFF...
  • Page 16 Wiring Diagram - AN035NSEDAV/AA...
  • Page 17 Wiring Diagram - AN075NSEDAV/AA...
  • Page 18 Wiring Diagram - AN120NSEDAV/AA...
  • Page 19: Wiring Diagram

    WIRING DIAGRAM (CONT'D) WIRING DIAGRAM Standard Accessory Control Contact TO FURNACE THERMOSTAT TERMINALS FOUR WIRE TWO WIRE heating only FOR A FURNACE CONNECTION TO A COOLING SYSTEM: On some newer furnaces and FURNACE older thermostats, energizing the 24-VOLT TERMINAL BLOCK R and G terminal at the furnace COOLING SYSTEM has the effect of energizing the Y...
  • Page 20: Installation Verification Test

    Installation Verification Test Without external control 1. Fan speed selector switch • Set fan Speed selector switch to Standby. 2. Start-up • Apply power to unit • Unit should enter Exhaust only defrost mode for a 10 second duration and the following should occur: Exhaust fan runs in HIGH (Normal) speed Supply fan remains off 3.
  • Page 21 Limited Warranty • 3 Year Warranty. • Fresh Access ERV's have a warranty that is limited to 3 years on all parts from the date of purchase, including parts replaced during this time period. If there is no proof of purchase available, the date associated with the serial number will be used for the beginning of the warranty period.
  • Page 22 (a) who holds a current government issued license that authorizes the individual For a full list of terms, conditions and exclusions, please visit our website at www.samsunghvac.com For questions regarding product registration, please contact your local Samsung Representative.
  • Page 24 Manuel d'installation Commerciaux Ventilateur récupérateur d'énergie AN035NSEDAV/AA, AN075NSEDAV/AA, AN120NSEDAV/AA Votre système de ventilation doit être installé conformément aux exigences de la province où vous habitez ou, à défaut de telles exigences, conformément à l’édition actuelle du Code national du bâtiment du Canada ou aux «...
  • Page 25 Avertissement/ Note Information Information Conseil Note importante technique pratique S'IL VOUS PLAÎT LIRE CE MANUEL AVANT L'INSTALLATION DE L'APPAREIL Avant de procéder à l’installation, examinez avec soin la façon dont le système fonctionnera s’il est relié à tout autre appareil mécanique, notamment une fournaise à air pulsé ou un appareil de traitement d’air dont la pression statique est plus élevée.
  • Page 26 Table des matières INSTALLATION Emplacement............. . . 23 Configuration des ports.
  • Page 27: Installation

    Installation EMPLACEMENT Le ventilateur-récupérateur d'énergie doit être situé dans un endroit chauffé où il est possible d'en faire l'entretien facilement. Généralement, le ventilateur-récupérateur d'énergie se situe dans la chambre des appareils mécaniques, au-dessus d'un plafond suspendu ou dans un endroit près du mur extérieur où on installera les capots. On ne recommande habituellement pas les installations dans les greniers en raison des températures extrêmes qu'on peut y retrouver et de la difficulté...
  • Page 28: Configuration Des Ports

    Configuration des ports L'appareil possède des portes d'accès à l'avant et l'arrière. De plus, on peut déplacer le panneau de commande principal de l'avant vers l'arrière, afin de faciliter la configuration du système de gaines. AN035NSEDAV/AA, AN075NSEDAV/AA Côté chaud Côté frois Côté...
  • Page 29: Installer La Conduite De Récupération Desfluides

    Installer la conduite de récupération des fluides Lors de son fonctionnement normal et lorsqu'il est en mode de dégivrage, le VRE peut produire de la condensation. L'eau ainsi produite doit être drainée ou retirée à l'aide d'une pompe à condensats. On doit installer le ventilateur-récupérateur de chaleur et tous les conduits de condensats dans un endroit où...
  • Page 30: Équilibrage Du Débit D'air

    Installation des conduits intérieurs Pour maximiser le débit d'air dans le système de gaines, on doit tenir ces dernières courtes et exemptes du plus de coudes possible. Les coudes à 45 degrés sont préférables à ceux à angle droit. Utiliser des raccords en « Y » plutôt que des T, lorsque cela est possible.
  • Page 31: Exemples D'installation

    Exemples d'installation Les dessins ne sont que des illustrations et les emplacements des entrées réelles et les directions des débits d'air peuvent varier. Consulter les fiches signalétiques des appareils. L'installateur doit s'assurer d'installer et de dimensionner tous les systèmes de gaines comme indiqué, afin que le système fonctionne comme prévu.
  • Page 32: Système Partiellement Dédidé (Connexion Indirecte)

    Exemples d'installation (Suite) Les dessins ne sont que des illustrations et les emplacements des entrées réelles et les directions des débits d'air peuvent varier. Consulter les fiches signalétiques des appareils. L'installateur doit s'assurer d'installer et de dimensionner tous les systèmes de gaines comme indiqué, afin que le système fonctionne comme prévu.
  • Page 33: Modes D'opération

    Modes d'opération 1. Mode continu / de ventilation Dans ce mode de fonctionnement, les deux ventilateur fonctionnent et échangent l'air avec l'extérieur. Le ventilateur récupérateur d'énergie (VRE) échange continuellement l'air à la vitesse que vous choisissez, soit à basse ou moyenne vitesse, et passe en haute vitesse lorsqu'il est activé...
  • Page 34: Configurer La Vitesse

    Configurer la vitesse (AN120NSEDAV/AA) AVERTISSEMENT ASSUREZ-VOUS QUE L'ALIMENTATION DE L'UNITÉ EST DÉCONNECTÉE AVANT DE FAIRE DES CHANGEMENTS Le VRE est expédié de l'usine à basse vitesse, un fonctionnement intermittent peut être obtenu par un commutateur de basculement situé à l'extérieur de l'armoire. La sélection de la tension pour la basse vitesse (réduite) de l'unité...
  • Page 35 SYSTÈME DE CONTRÔLE À BASSE TENSION * Veuillez voir les instructions individuelles des contrôles pour le câblage et la mise en pièce appropriée. CONTRÔLES CENTRALS Ces options de contrôle peuvent seulement être utilisé individuellement CONTRÔLE CARACTÉRISTIQUES CONNEXION À ECO-Touch® • Notre système de contrôle le plus complet, mais facile à...
  • Page 36: Entretien

    Entretien AVERTISSEMENT S'ASSURER QUE L'APPAREIL EST DÉBRANCHÉ AVANT D'Y RÉALISER TOUT TRAVAIL D'ENTRETIEN On doit aussi inspecter les composants suivants régulièrement et les entretenir adéquatement. Moteur - Les moteurs sont équilibrés en usine et lubrifiés à vie. Ils ne nécessitent aucun entretien Appareil - On doit nettoyer l'intérieur de l'appareil à...
  • Page 37: Connexions Électriques

    Connexions électriques - AN035NSEDAV/AA...
  • Page 38 Connexions électriques - AN075NSEDAV/AA...
  • Page 39 Connexions électriques - AN120NSEDAV/AA...
  • Page 40 SCHÉMAS ÉLECTRONIQUES (SUITE) Standard Furnace Interlock Wiring THERMOSTAT TERMINALS FOUR WIRE TWO WIRE heating only RV-CTRL 24VAC FURNACE 24-VOLT TERMINAL BLOCK COOLING SYSTEM WIRE Standard Furnace Interlock Wiring (w/Damper) THERMOSTAT TERMINALS FOUR WIRE TWO WIRE heating only RV-CTRL 24VAC FURNACE 24-VOLT TERMINAL BLOCK COOLING SYSTEM...
  • Page 41 Alternate Furnace Interlock Wiring THERMOSTAT TERMINALS FOUR WIRE TWO WIRE heating only RV-CTRL 24VAC FURNACE 24-VOLT TERMINAL BLOCK COOLING SYSTEM WIRE Alternate Furnace Interlock Wiring (w/Damper) THERMOSTAT TERMINALS FOUR WIRE TWO WIRE heating only RV-CTRL 24VAC FURNACE 24-VOLT TERMINAL BLOCK COOLING SYSTEM WIRE SHUTOFF...
  • Page 42: Test De Vérification De L'installation

    Test de vérification de l'installation Sans contrôle externe 1. Commutateur de sélection de vitesse du ventilateur • Réglez le sélecteur de vitesse du ventilateur en mode Attente (Standby) 2. Mise en service • Placez l'appareil en marche • L'appareil devrait être en mode de dégivrage par évacuation seulement pour une durée de 10 secondes et les suivants devraient se produire: Ventilateur d'évacuation fonctionne à...
  • Page 43 Garantie limitée • Garantie de 3 ans. • Les ventilateurs-récupérateurs d'énergie Fresh Access détiennent une garantie de trois (3) ans sur toutes les pièces à partir de la date d'achat, y compris les pièces remplacées pendant cette période. Si aucune preuve d'achat n'est disponible, on utilisera la date associée au numéro de série comme date d'entrée en vigueur de la garantie.
  • Page 45 Fresh Access reserves the right to make technical changes. For updated documentation please refer to www.SamsungHVAC.com. Fresh Access se réserve le droit de faire des changements techniques. Pour de la documentation à jour, s'il vous plaît se référer au www.SamsungHVAC.com.

This manual is also suitable for:

Fresh access an075nsedav/aaFresh access an120nsedav/aa

Table of Contents