Summary of Contents for Inepro PRO1 Series

  • Page 1 PRO1 series DIN rail single phase two wire energy meter PRO1D V11.112 PRO1D V11.121 PRO1D V11.122 PRO1D V11.211 PRO1D V11.212 PRO1D V11.221 PRO1D V11.222 PRO1TE V11.311 PRO1TE V11.312 PRO1TE V11.321 PRO1TE V11.322 Version 1.0 Note: the picture on the frontpage is a meter from the series of this meter, it might not...
  • Page 2: Table Of Contents

    Safety instructions ................3 Foreword .................... 4 Type number table ................4 MID certificate ..................5 Performance criteria ................6 Specifications ..................6 Basic errors ..................7 Description ..................7 Dimensions ..................8 10 Torque tables ..................8 11 Installation ..................8 12 Operation ...................
  • Page 3: Safety Instructions

    Use for the intended purpose This device may only be used for the application cases specified in the catalog and the user manual and only in connection with devices and components recommended and approved by Inepro Metering B.V. Proper handling The prerequisites for perfect, reliable operation of the product are proper transport, storage, installation and connection, as well as proper operation and maintenance.
  • Page 4: Foreword

    It is prohibited to pass on or copy this document or to use or disclose its contents without express permission of Inepro Metering BV. Any duplication is a violation of the law and subject to criminal and civil penalties. All rights reserved, particularly for pending or approved patent awards or registered trademarks.
  • Page 5: Mid Certificate

    4 MID certificate ® 2011 - 5 - For the SOP number see section 15 PRO1 V11.xxx...
  • Page 6: Performance Criteria

    5 Performance criteria Operating humidity ≤ 75% Storage humidity ≤ 95% Operating temperature -25°C - +55°C Storage temperature -25°C - +55°C International standard EN 50470-1 and 50470-3 Accuracy class Protection against penetration of dust and water IP51 Insulating encased meter of protective class 6 Specifications Meter type...
  • Page 7: Basic Errors

    7 Basic errors 0.05Ib Cosφ = 1 ±1.5% 0.1Ib Cosφ = 0.5L ±1.5% Cosφ = 0.8C ±1.5% 0.1Ib - Imax Cosφ = 1 ±1.0% 0.2Ib - Imax Cosφ = 0.5L ±1.0% Cosφ = 0.8C ±1.0% 8 Description Display register Case Protection cover Security wire slot Material...
  • Page 8: Dimensions

    9 Dimensions Height 120 mm Height without protection cover 92 mm Width 18 mm Depth 63.5 mm Size of the connection clamps 4 x 4 mm Weight 0.08 kg (net) 10 Torque tables Screw Terminal Terminals Max wire size (mm Torque driver 4.0±0.25(kgf.cm)
  • Page 9: Operation

    LED, please don’t get confused). 12.2 Reading the meter The PRO1 series meter can be delivered with either a digital or mechanical register. See the version numbering in section 1.3. 12.3 Mechanical register The PRO1TE series energy meter is equipped with a mechanical 5+1 register which is used to record consumption and can’t be reset to zero.
  • Page 10: Digital Register

    12.4 Digital register The PRO1D series energy meter is equipped with a 5+2 digit LCD which is used to record consumption and can’t be reset to zero. The display has 5 digits before and 2 decimals after the dot on the display. The reading accuracy is 1/100 kWh. For this meter, the LED will flash 1000 or 2000 times per kWh depending on the version of the meter, see section 0 for details.
  • Page 11: Troubleshooting

    13 Troubleshooting CAUTION During repair and maintenance, do not touch the meter connecting clamps directly with your bare hands, with metal, blank wire or other conducting material as that will cause an electric shock and possibly cause injury, serious injury or even death. Turn off and if possible lock all sources supplying the energy meter and the equipment that is connected to it before opening the protection cover and working on it.
  • Page 12: Technical Support

    14 Technical support For questions about one of our products please contact: Your local Inepro Metering distributor Email: support@ineprometering.com www.ineprometering.com 15 SOP Table PRO1D V11.111 (mold C) 0059 PRO1D V11.112 (mold C) 0060 PRO1D V11.121 (mold C)

Table of Contents