Inepro DMMetering PRO1250D User Manual

Inepro DMMetering PRO1250D User Manual

Din rail three phase four wire energy meter

Advertisement

PRO1250D CT M-bus MID
DIN rail three phase four wire energy meter.
User manual
Version 1.11

Advertisement

Table of Contents
loading

Summary of Contents for Inepro DMMetering PRO1250D

  • Page 1 PRO1250D CT M-bus MID DIN rail three phase four wire energy meter. User manual Version 1.11...
  • Page 2: Table Of Contents

    Safety instructions .....................3 Foreword ........................4 MID certificate......................5 CE certificates ......................6 Performance criteria ....................8 Specifications ......................8 Basic errors ......................8 Description .......................9 10 Dimensions .......................9 11 M-bus communication specifications................10 12 Installation ......................10 13 Operation ....................... 11 13.1 Working indication ..................... 11 13.2 Consumption indication ..................
  • Page 3: Safety Instructions

    Use for the intended purpose This device may only be used for the application cases specified in the catalog and the user manual and only in connection with devices and components recommended and approved by Inepro Metering B.V. Proper handling The prerequisites for perfect, reliable operation of the product are proper transport, storage, installation and connection, as well as proper operation and maintenance.
  • Page 4: Foreword

    It is prohibited to pass on or copy this document or to use or disclose its contents without express permission of Inepro Metering BV. Any duplication is a violation of the law and subject to criminal and civil penalties. All rights reserved, particularly for pending or approved patent awards or registered trademarks.
  • Page 5: Mid Certificate

    MID certificate ® 2011 - 5 - PRO1250D CT M-bus MID User manual 0151...
  • Page 6: Ce Certificates

    CE certificates ® 2011 - 6 - PRO1250D CT M-bus MID User manual 0151...
  • Page 7 ® 2011 - 7 - PRO1250D CT M-bus MID User manual 0151...
  • Page 8: Performance Criteria

    Performance criteria Operating humidity ≤ 75% Storage humidity ≤ 95% Operating temperature -25°C - +55°C Storage temperature -25°C - +55°C International standard EN50470-3 and EN13757 Accuracy class Protection against penetration of dust and water IP51 Insulating encased meter protective class Ⅱ...
  • Page 9: Description

    Description Front panel Cover Case Security wire slot Material Front panel PC flame resistant plastic Cover ABS flame resistant plastic Case ABS flame resistant plastic 10 Dimensions Height with protection cover 130 mm Height without protection cover 100 mm Width 126 mm Depth 65/59,5 mm...
  • Page 10: Bus Communication Specifications

    11 M-bus communication specifications Bus type M-bus baud rate 300, 2400 (default),9600 Range ≤380m 250PCS ≤3600m 64PCS Cable JYSTY (n×2×0.8) Protocol EN13757-3 Max. number of meters *Note that the maximum number of meters is dependent on the converter, baudrate (the higher the baudrate the smaller the number of meters which can be used) and the circumstances under which the meters are installed.
  • Page 11: Operation

     The device can be installed on a 35mm DIN rail  The meter should be installed on a location where the meter can be read easily.  In case the meter is installed in an area with frequent surges for example due to thunderstorms, welding machines, inverters etc, the meter is required to be protected with a Surge Protection Device.
  • Page 12: Consumption Indication

    13.2 Consumption indication There is a red LED at the right side of the display with the text (1600 imp/Kwh), which displays the consumption measured by the meter. When power is consumed, the LED will flash. The faster the LED flashes, the more power is consumed. For this meter, the LED will flash 1600 times per kWh.
  • Page 13: Ct Ratio Settings

    14 CT ratio settings How to set the CT ratio of the meter The default CT ratio is 5:5. In case you want to change the CT ratio to another setting, you have 27 options, but you can only change the default CT-ratio once for this meter. It’s advised to set the CT-ratio immediately after installing the meter.
  • Page 14: Troubleshooting

    15 Troubleshooting CAUTION  During repair and maintenance, do not touch the meter connecting clamps directly with your bare hands, with metal, blank wire or other conducting material as that will cause an electric shock and possibly cause injury, serious injury or even death. ...
  • Page 15 Problem Possible cause Check/solution No pulse output. The pulse output is Check the external voltage source not supplied with (Ui) is 5-27V DC with a voltage DC power meter The pulse output is Check if the connection is correct: connected 5-27V should correctly...
  • Page 16 Problem Possible cause Check/Solution The power supply meter is not fuses or/and surge indicators (L1, L2 & connected protection defect? L3 LED) are off. power source L1, L2, L3 and N are Make sure wires connected connected properly and tighten correctly the screws if possible.
  • Page 17 Maybe there is a Please contact technical support fault inside the for a meter replacement. meter. ® 2011 - 17 - PRO1250D CT M-bus MID User manual 0151...
  • Page 18: Technical Support

    16 Technical support For questions about one of our products please contact: Your local Inepro Metering distributor Email: support@ineprometering.com www.ineprometering.com ® 2011 - 18 - PRO1250D CT M-bus MID User manual 0151...