Inepro 4PU Series User Manual

Inepro 4PU Series User Manual

Three phase energy meter

Advertisement

4PU and 4PS Series MID
Three phase energy meter
User manual
Version: 1.00
© 2021 Inepro B.V. All rights reserved

Advertisement

Table of Contents
loading

Summary of Contents for Inepro 4PU Series

  • Page 1 4PU and 4PS Series MID Three phase energy meter User manual Version: 1.00 © 2021 Inepro B.V. All rights reserved...
  • Page 3: Table Of Contents

    Appendix 4 - Bluetooth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Inepro Metering - 4PU & 4PS - 3...
  • Page 4: Safety Instructions

    Use for the intended purpose This device may only be used for the application cases specified in the catalog and the user manual and only in connection with devices and components recommended and approved by Inepro Metering B.V. Proper handling The prerequisites for perfect, reliable operation of the product are proper transport, storage, installation and connection, as well as proper operation and maintenance.
  • Page 5 It is prohibited to pass on or copy this document or to use or disclose its contents without express permission of Inepro Metering BV. Any duplication is a violation of the law and subject to criminal and civil penalties. All rights reserved, particularly for pending or approved patent awards or registered trademarks.
  • Page 6: Foreword

    3 Foreword Thank you for purchasing this energy meter. Inepro has a wide product range of devices. We have introduced a large number of energy meters on the market suitable for 110V AC to 400V AC (50 or 60Hz). Besides the normal energy meters we also developed our own pre-paid meters with chip card, chip card re-loaders and a complete PC management control system.
  • Page 7: Certificates

    Following the provisions of the Directives (if applicable): specifications 2014/32/EU (MID)  2011/65/EU (RoHS)  1907/2006 (REACH)  2014/53/EU (RED)  Nieuw-Vennep, 08-03-2021 Place and date of issue D. van der Vaart Name of responsible for CE-marking Inepro Metering - 4PU & 4PS - 7...
  • Page 8: Specifications

    Storage humidity ≤ 95% International standard EN50470-1/3 Accuracy class B (=1% accuracy) Protection against penetration of dust and water IP51 Insulating encased meter of protective class Operating temperature range -40°C - +70°C 8 - Inepro Metering - 4PU & 4PS...
  • Page 9: Basic Errors

    300, 600, 1200, 2400 (default), 4800 and 9600 Range ≤1000m Downlink signal Master to slave. Voltage modulation Uplink signal Slave to master. Current modulation Cable JYSTY (nx2x0,8) Protocol EN13757-3 Unit loads Max. number of meters 64 per bus* Inepro Metering - 4PU & 4PS - 9...
  • Page 10: Rs485 Communication Specifications

    0.2 … 4 mm² / 24 … 12 AWG Fine-stranded conductor; with insulated ferrule 0.25 … 2.5 mm² Push-in technology can be used for Solid conductors and fine-stranded conductors with insulated ferrule. Fine-stranded conductors require opening the levers for connection. 10 - Inepro Metering - 4PU & 4PS...
  • Page 11: Connection Diagram

    5 Ground (-) 6 S0 output 2 (+) 7 Modbus communication contact A 8 Modbus communication contact B / M-bus communication contact 9 M-bus communication contact 10, 11: Tariff switching (230V AC) Inepro Metering - 4PU & 4PS - 11...
  • Page 12 6 S0 output 2 (+) S0 1 7 Modbus communication contact A 8 Modbus communication contact B / M-bus communication contact S0 2 9 M-bus communication contact 10, 11: Tariff switching (230V AC) B/BUS2 BUS1 12 - Inepro Metering - 4PU & 4PS...
  • Page 13: Installation

    In case the meter is installed in an area with frequent surges for example due to thunderstorms, welding machines, inverters etc., the meter is required to be protected with a Surge Protection Device. • The device should be sealed immediately after installing it in order to prevent tampering. Inepro Metering - 4PU & 4PS - 13...
  • Page 14: Operation

    Scroll through the display pages (Total - L1 - L2 -L3) using the capacitive touch buttons on the frontside of the meter. 14 - Inepro Metering - 4PU & 4PS...
  • Page 15: Settings

    Activate settings mode by holding the middle button (*) for >3 seconds. The following display will appear: 7 .5 Bluetooth Press the middle button to activate Bluetooth: Scan the QR code on the display using the inepro Metering mobile phone app. Inepro Metering - 4PU & 4PS - 15...
  • Page 16: Button Settings

    When Bluetooth connection is active, the Bluetooth activation icon will be show on the display: Go to Appendix 4 - Bluetooth for the inepro Metering mobile phone app user guide. 7 .6 Button settings Settings can also be done using the capacitive touch buttons on the front of the meter. Scroll through the options using the left <<...
  • Page 17: Password

    The default imp/kWh setting for the S0 output is 1.000. The S0 output setting can be modified to 10.000 / 2.000 / 100 / 10 / 1 / 0,1 / 0,01 imp/kWh. Inepro Metering - 4PU & 4PS - 17...
  • Page 18: Pulse Type Setting

    The default Modbus baud rate setting is 9600. The Modbus baud rate setting can be modified to 115.200 / 56.700 / 38.400 / 19.200 / 4800 / 2400 / 1200 / 600 / 300 bps. 18 - Inepro Metering - 4PU & 4PS...
  • Page 19: Modbus Parity

    7 .6 .10 M-bus baud rate The default M-bus baud rate setting is 2400. The Modbus baud rate setting can be modified to 9600 / 4800 / 1200 / 600 / 300 bps. Inepro Metering - 4PU & 4PS - 19...
  • Page 20: Backlight

    The meter is equipped with a trip counter that can be set to zero by the user. This is the energy calculated based on the combination code setting (see 7.6.15). 7 .6 .14 OBIS codes OBIS codes can be used to identify the corresponding measurement values. OBIS codes are turned off by default. 20 - Inepro Metering - 4PU & 4PS...
  • Page 21: Combination Code (Modbus, M-Bus & Bluetooth Setting Only)

    -12 kWh LCD reading and calculation of total energy Code C-01 C-02 C-03 C-04 C-05* Total Forward Reverse *Meters ordered or set afterwards to C-05 cannot be set to another calculation mode. Inepro Metering - 4PU & 4PS - 21...
  • Page 22: Troubleshooting

    5-27V DC should be connected to the collector connection (pin 18/20+) and the signal wire (S) to the emitter con- nection (pin 19/21-). If none of the above works, please contact technical support 22 - Inepro Metering - 4PU & 4PS...
  • Page 23: Errors / Diagnostics Display

    Data error in the main battery storage area (integer bit) bit7: EEPROM cannot be fully initialized 8 .2 Technical support For questions about one of our products please contact: • Your local Inepro Metering distributor • Email: support@ineprometering.com • Website: www.ineprometering.com Inepro Metering - 4PU & 4PS - 23...
  • Page 24: Appendix 1 - Multi Tariff Function

    T3 and T4 can only be activated by Bluetooth, Modbus, M-bus or using the button function. After activating T3 and/or T4 once, the energy values per tariff (3 / 4) will be displayd in the MID relevant part of the display. This cannot be undone . 24 - Inepro Metering - 4PU & 4PS...
  • Page 25: Appendix 2 - M-Bus

    For the registers used in the meter and how to interpreted the data, please use the M-bus register map on the next page. More detailed information on M-Bus can be found: www.m-bus.com Inepro Metering - 4PU & 4PS - 25...
  • Page 26: A2.2 M-Bus Register Map

    FD 3A 00 01 50,999Hz Grid frequency FB 2C 37 C7 00 Tariff 7C 01 54 9995/5 CT rate (only for CT version) FD 3A 05 95 99 xx 16 Checksum xx xx 26 - Inepro Metering - 4PU & 4PS...
  • Page 27 Manufacturer ID Generation version Medium 68 0B 0B 68 53 FD 52 aa aa aa aa bb bb Input 01 00 07 13 CD 25 Remarks 13070001 Major version of the software Electricity Inepro Metering - 4PU & 4PS - 27...
  • Page 28: Appendix 3 - Modbus

    For the registers used in the meter and how to interpreted the data, please use the Modbus register map on the next pages. More info on Modbus can be found: Physical: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf Protocol: http://www.modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf 28 - Inepro Metering - 4PU & 4PS...
  • Page 29: A3.2 Modbus Register Map

    CT ratio Signed 9995 005 = 9995/5 4021 Pulse width Signed Value between 2-99 ms 4022 Pulse type setting 1: active & reactive 2: forward & reverse 4023 Checksum 2 (non-relevant) 4025 Reserved Inepro Metering - 4PU & 4PS - 29...
  • Page 30 Power factor Float ABCD 502C L1 Power factor Float ABCD 502E L2 Power factor Float ABCD 5030 L3 Power factor Float ABCD 5032 L1-L2 Voltage Float ABCD 5034 L1-L3 Voltage Float ABCD 30 - Inepro Metering - 4PU & 4PS...
  • Page 31 6032 T1 Forward reactive energy kvarh Float ABCD 6034 T2 Forward reactive energy kvarh Float ABCD 6036 L1 Forward reactive energy kvarh Float ABCD 6038 L2 Forward reactive energy kvarh Float ABCD Inepro Metering - 4PU & 4PS - 31...
  • Page 32 Float ABCD 606F 6071 Imp. capacitive reactive energy in Q2 (T2) Float ABCD Imp. capacitive reactive energy in Q2 (T3) Float ABCD 6073 Imp. capacitive reactive energy in Q2 (T4) Float ABCD 6075 32 - Inepro Metering - 4PU & 4PS...
  • Page 33 Exp. capacitive reactive energy in Q4 (T4) Float ABCD 608B Resettable day counter L1 Float ABCD 608D Resettable day counter L2 Float ABCD 608F Resettable day counter L3 Float ABCD *PRO series only Inepro Metering - 4PU & 4PS - 33...
  • Page 34 01 06 4032 0001 (new setting: turn 180 degrees) 0: standard - 1: turn 180 degrees Command: 4033 0 = OSigned OBIS code ON/OFF 01 06 4033 0001 (new setting: OBIS ON) 0: OFF - 1: ON Command: *2PCT only 34 - Inepro Metering - 4PU & 4PS...
  • Page 35: Appendix 4 - Bluetooth

    Appendix 4 - Bluetooth All Ambition meters are capable to be read out and configured by Bluetooth communication. You can download the inepro Meter Manager app for android or IOS in the stores. Download on the App Store: Download on the Google Play store: A 4 .1 Bluetooth app...
  • Page 36 Select the correct serial number for connection. 2. Scan QR: the app opens the mobile phone camera to scan the QR code on the meter display. Once scanned, the meter is connected. 36 - Inepro Metering - 4PU & 4PS...
  • Page 37 A 4 .3 Device connected The meter is now connected to the mobile phone app. The device page shows the meter type, serial number and softare version. Read data by selecting Energy values or Instantaneous values: Inepro Metering - 4PU & 4PS - 37...
  • Page 38 Read data by selecting Energy values or Instantaneous values: Refresh the data using the refresh button in the right upper corner. Save the data using the save button. Data can be saved and shared to different mobile phone applications. 38 - Inepro Metering - 4PU & 4PS...
  • Page 39 Settings Settings can selected individualy and/or saved all at once. Select the settings that need to be modified. The modified settings will be marked green. Inepro Metering - 4PU & 4PS - 39...
  • Page 40 Press the Save button to store the settings in the meter. First a pop-up menu for password will appear. The default password is 0000. The password can only be modified in the meter using the buttons. After entering the correct pass- word the new settings will be stored in the meter: 40 - Inepro Metering - 4PU & 4PS...
  • Page 41 Inepro Metering - 4PU & 4PS - 41...