Download Print this page

ICP DAS USA SG-3081 User Manual page 2

Isolated current input / output module

Advertisement

Configuration
The terminal wiring for the SG-3081 is shown in Figure A. Positive power terminals pins 7 and
9 are internally connected, as are negative pins 10 and 12. Power can be connected through
the adjacent modules, making wiring much easier. The SG-3081 uses a power input range of
10~30Vdc.
Table 1 shows the switch positions used to configure the input and output range.
The I/O configuration switches are located inside the module. And can be accessed by
removing the DIN-rail bracket covers by sliding them in the direction shown in Figure B.
SG3081
Input To Output
Range
4~20mA/4~20mA
4~20mA/0~20mA
4~20mA/0~10V
4~20mA/0~5V
0~20mA/0~20mA
0~20mA/4~20mA
0~20mA/0~10V
0~20mA/0~5V
*
Range (SW1)
1
2
3
4
5
Table 1: Input to output range (SW1, 2, Jumper1, 2)
* Factory default setting
Range (SW2)
6
1
2
3
4
◆ ◆
◆ ◆
◆ ◆
2
Jumper
5
6
7
8
1
◆ ◆ ◆ ◆
◆:ON
2

Advertisement

loading