Electrical wiring work

Specification of the circuit breaker and power cable

Electric Characteristics
Norm. Ton
Model
10
AG010KSVAFH
15
AG015KSVAFH
10
AG010KSVAJH
15
AG015KSVAJH
1)
Rated Load Ampere
2)
Full Load Ampere
NOTE
RLA is based on AHRI 1230 Cooling Standard Condition.
- Indoor temperature: 26.7°C (80°F) DB / 19.46°C (67°F) WB
- Outdoor temperature: 35°C (95°F) DB
Voltage tolerance is ± 10%.
Maximum allowable voltage between phases is 2%.
Refer to module combination table for independent unit's information.
CAUTION
You must install ELCB or MCCB + ELB
- ELCB: Earth leakage circuit breaker
- MCCB: Molded Case Circuit Breaker
- ELB: Earth Leakage fuse Breaker
Do not operate the outdoor unit before completing the refrigerant pipe work.
Do not disconnect or change the cable inside the product. It may cause damage to the product.
Specification of the power cable is selected based on following installation condition; culvert installation/
ambient temperature 30°C (86°F)/ single multi conductor cables. If the condition is different from the ones
stated, please consult an electrical installation expert and reselect the power cable.
- If the length of power cable exceeds 50 m (164.04 ft), reselect the power cable considering the voltage
drop.
Use a power cable made out of incombustible material for the insulator (inner cover) and the sheath (outer
cover).
Do not use the power cable with the core wire
exposed due to insulator damage occurred during
removal of the sheath. When the core wire is exposed,
it may cause fire.
Units
Hz
Volts
RLA
1)
#1
60
208/230
19.5
60
208/230
27.5
60
460
8.8
60
460
16
3)
Minimum Circuit Ampere (A)
4)
Maximum Overcurrent Protective Device (A)
Comp
Fan motor
RLA
1)
#2 FLA
2)
#1 FLA
19.5
4
27.5
4
8.8
2
16
2
Example of exposed core wire
Exposed
wire core
MCA
3)
MOP
4)
2)
#2
4
52
70
4
70
90
2
24
30
2
40
50
Insulator
(inner cover)