Three-phase asymmetry and phase-sequence phase-loss relay (23 pages)
Summary of Contents for Omron K8AK-VW2 24 VAC/DC
Page 1
For the most recent information on models that have been certified for • Inputs are isolated from the power supply. safety standards, refer to your OMRON website. Refer to Safety Precautions on page 9. Refer to page 8 for commonly asked questions.
Page 2
K8AK-VW Ratings Power supply 24 VAC/DC Isolated power supply voltage 100 to 240 VAC 24 VAC/DC: 2.0 VA/1.1 W max. Power consumption 100 to 240 VAC: 4.6 VA max. 10% to 100% of the maximum value of the setting range K8AK-VW2: 1 to 10 V AC/DC 3 to 30 V AC/DC Operating value setting range (AL1 and AL2)
K8AK-VW Specifications Allowable operating voltage range 85% to 110% of rated power supply voltage 50/60 Hz ±5 Hz Allowable operating frequency range Input frequency range 40 to 500 Hz Overload capacity Continuous input at 115% of maximum input, 10 s at 125% (up to 600 VAC). ±0.5% full scale (at 25°C and an ambient humidity of 65% at the rated power supply voltage, DC and 50/60 Operating value Hz sine wave input)
K8AK-VW Wiring Example Single-phase Load power supply Power supply AC/DC Power supply voltage Timing Charts ●Overvoltage and Undervoltage Operation ●Undervoltage and Undervoltage Operation Diagram Diagram (Undervoltage Pre-alarm Mode) DIP switch settings: SW3 and SW4 both ON or both OFF. DIP switch settings: SW3 OFF and SW4 ON. Power supply voltage Power supply voltage Input...
Page 5
K8AK-VW Nomenclature ●Indicators Front Item Meaning Terminal block Power indicator (See notes 1 and 2.) Lit when power is being supplied. (PWR: Green) Lit when relay operates (Not light when Relay status indicator both AL1 and AL2 are in error status) (Nor- (RY: Yellow) mally lit) Lit when there is an overvoltage or under-...
K8AK-VW Operation Methods Setting Ranges and Wiring Connections Model Setting range Wiring connection 1 to 10 V AC/DC V1-COM K8AK-VW2 3 to 30 V AC/DC V2-COM 15 to 150 V AC/DC V3-COM 20 to 200 V AC/DC V1-COM K8AK-VW3 30 to 300 V AC/DC V2-COM 60 to 600 V AC/DC V3-COM...
K8AK-VW Setting Method ●Setting Voltage ●Operating Time The voltage knob (AL1 and AL2) is used to set the voltage. The operating time is set using the operating time knob (T). The voltage can be set to 10% to 100% of the maximum setting The operating time can be set to between 0.1 and 30 s.
Page 8
K8AK-VW Questions and Answers How to Measure the Operating Time Checking Operation Overvoltage Overvoltages Change the input suddenly from 0% to 120% of the set value Gradually increase the input from 80% of the set value. and measure the time until the Unit operates. The input will equal the operating value when the input Undervoltage exceeds the set value and the alarm indicator starts flashing.
K8AK-VW Safety Precautions Be sure to read the precautions for all models in the website at the following URL: http://www.ia.omron.com/. Warning Indications WARNING Indicates a potentially hazardous situation which, if not avoided, will result in minor or Electrical shock may occasionally cause serious injury.
K8AK-VW Precautions for Safe Use Precautions for Correct Use 1. Do not use or store the product in the following locations. Observe the following operating • Locations subject to water or oil methods to prevent failure and • Outdoor locations or under direct sunlight malfunction.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements.