Precautions for Safe Use

1. Do not use or store the product in the following locations.
• Locations subject to water or oil
• Outdoor locations or under direct sunlight
• Locations subject to dust or corrosive gases (particularly
sulfurizing gases, ammonia, etc.)
• Locations subject to rapid temperature changes
• Locations prone to icing and dew condensation
• Locations subject to excessive vibration or shock
• Locations subject to wind and rain
• Locations subject to static electricity and noise
• Habitats of insects or small animals
2. Use and store the product in a location where the ambient
temperature and humidity are within the specified ranges. If
applicable, provide forced cooling.
3. Mount the product in the correct direction.
4. Check terminal polarity when wiring and wire all connections
correctly. The power supply terminals do not have polarity.
5. Do not wire the input and output terminals incorrectly.
6. Make sure the power supply voltage and loads are within the
specifications and ratings for the product.
7. Make sure the crimp terminals for wiring are of the specified size.
8. Do not connect anything to terminals that are not being used.
9. Use a power supply that will reach the rated voltage within 1
second after the power is turned ON.
10.Keep wiring separate from high voltages and power lines that
draw large currents.
Do not place product wiring in parallel with or in the same path as
high-voltage or high-current lines.
11.Do not install the product near equipment that generates high
frequencies or surges.
12.The product may cause incoming radio wave interference. Do not
use the product near radio wave receivers.
13.Install an external switch or circuit breaker and label it clearly so
that the operator can quickly turn OFF the power supply.
14.Make sure the indicators operate correctly. Depending on the
application environment, the indicators may deteriorate
prematurely and become difficult to see.
15.Do not use the product if it is accidentally dropped. The internal
components may be damaged.
16.Be sure you understand the contents of this catalog and handle
the product according to the instructions provided.
17.Do not install the product in any way that would place a load on it.
18.When discarding the product, properly dispose of it as industrial
waste.
19.When using the product, remember that the power supply
terminals carry a high voltage.
20.The product must be handled only by trained electrician.
21.Prior to operation, check the wiring before you supply power to
the product.
22.Do not install the product immediately next to heat sources.
23.Perform periodic maintenance.
10

Precautions for Correct Use

Observe the following operating
methods to prevent failure and
malfunction.
1. Use the power supply voltage, input power, and other power
supplies and converters with suitable capacities and rated
outputs.
2. Use a precision screwdriver or similar tool to adjust the setting
knobs.
3. Do not use the product in circuits with waveform distortion. Error
will be large due to waveform distortion.
4. Error will be large if the product is used for thyristor or inverter
control.
5. To reduce the error in the setting knob, always turn the setting
knob from the minimum setting toward the maximum setting.
6. When cleaning the product, do not use thinners or solvents. Use
commercial alcohol.
Correct Mounting Direction, Mounting,
and Removing
• Mounting to DIN Track
1. Attach the product to the DIN Track with the tab at the top and
the hooks at the bottom.
2. Push the product onto the Track until the hooks lock into place.
A
• Removing from the DIN Track
Pull down on the bottom hook with a flat-blade screwdriver and lift
up on the product.
Adjusting the Setting Knobs
• Use a screwdriver to adjust the setting knobs. The knobs have a
stopper that prevents them from turning beyond the full right or left
position. Do not force a knob beyond these points.
Setting knob
B
Applicable DIN Tracks:
PFP-100N (100 cm)
PFP-50N (50 cm)

Advertisement

Table of Contents