Three-phase asymmetry and phase-sequence phase-loss relay (23 pages)
Summary of Contents for Omron K8AK-VW3
Page 1
For the most recent information on models that have been certified for • Inputs are isolated from the power supply. safety standards, refer to your OMRON website. Refer to Safety Precautions on page 9. Refer to page 8 for commonly asked questions.
Page 2
K8AK-VW2: 1 to 10 V AC/DC 3 to 30 V AC/DC Operating value setting range (AL1 and AL2) 15 to 150 V AC/DC K8AK-VW3: 20 to 200 V AC/DC 30 to 300 V AC/DC 60 to 600 V AC/DC Operating value...
Page 3
K8AK-VW Specifications Allowable operating voltage range 85% to 110% of rated power supply voltage Allowable operating frequency range 50/60 Hz ±5 Hz Input frequency range 40 to 500 Hz Overload capacity Continuous input at 115% of maximum input, 10 s at 125% (up to 600 VAC). ±0.5% full scale (at 25°C and an ambient humidity of 65% at the rated power supply voltage, DC and 50/60 Operating value Hz sine wave input)
K8AK-VW Wiring Example Single-phase Load power supply Power supply AC/DC Power supply voltage Timing Charts ●Overvoltage and Undervoltage Operation ●Undervoltage and Undervoltage Operation Diagram Diagram (Undervoltage Pre-alarm Mode) DIP switch settings: SW3 and SW4 both ON or both OFF. DIP switch settings: SW3 OFF and SW4 ON. Power supply voltage Power supply voltage Input...
Page 5
K8AK-VW Nomenclature ●Indicators Front Item Meaning Terminal block Power indicator (See notes 1 and 2.) Lit when power is being supplied. (PWR: Green) Lit when relay operates (Not light when Relay status indicator both AL1 and AL2 are in error status) (Nor- (RY: Yellow) mally lit) Lit when there is an overvoltage or under-...
V1-COM K8AK-VW2 3 to 30 V AC/DC V2-COM 15 to 150 V AC/DC V3-COM 20 to 200 V AC/DC V1-COM K8AK-VW3 30 to 300 V AC/DC V2-COM 60 to 600 V AC/DC V3-COM Connections ●Input Single-phase power Connect the input between terminals V1-COM, V2-COM, or V3-COM, depending on the input voltage.
Page 7
Use this as a guide to set the voltage. The maximum setting range will differ depending on the model and the input terminal. Example: K8AK-VW3 Using Input Terminal V3-COM The maximum setting range will be 600 VAC/VDC and the setting range will be 60 to 600 V.
K8AK-VW Questions and Answers How to Measure the Operating Time Checking Operation Overvoltage Overvoltages Change the input suddenly from 0% to 120% of the set value Gradually increase the input from 80% of the set value. and measure the time until the Unit operates. The input will equal the operating value when the input Undervoltage exceeds the set value and the alarm indicator starts flashing.
K8AK-VW Safety Precautions Be sure to read the precautions for all models in the website at the following URL: http://www.ia.omron.com/. Warning Indications WARNING Indicates a potentially hazardous situation which, if not avoided, will result in minor or Electrical shock may occasionally cause serious injury.
Page 10
K8AK-VW Precautions for Safe Use Precautions for Correct Use 1. Do not use or store the product in the following locations. Observe the following operating • Locations subject to water or oil methods to prevent failure and • Outdoor locations or under direct sunlight malfunction.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements.