Locations To Avoid - Ei Electronics Ei161e Instruction Manual

230v smoke & heat alarms with rechargeable battery backup
Hide thumbs Also See for Ei161e:
Table of Contents

Advertisement

Positioning Alarms
T
he locations must comply with applicable building
regulations.
Hot smoke rises and spreads out, so a central ceiling
position is the preferred location. The air is "dead" and does
not move in corners, therefore Smoke & Heat Alarms must
be mounted away from corners. Place the unit:
- At least 0.3m away from walls. See Figure 1.
- At least 0.3m from any light fitting or decorative object
which might obstruct smoke / heat entering the Alarm.
0.3m
Figure 1
Sloping Ceiling
With a sloping or peaked ceiling install a Smoke Alarm
within 600mm of the peak or a Heat Alarm within 150mm
of the peak (measured vertically). If this height is less
than 600mm for Smoke Alarms or 150mm for Heat
Alarms it is regarded as being flat (see Figure 2).
Wall mounting of smoke alarms (only):
If ceiling mounting is impractical, smoke alarms may
be mounted on a wall, provided that:
a) the top of the detection element is between
150mm and 300mm below the ceiling;
b) the bottom of the detection element is above the
level of any door openings;
Wall mounting should only be considered where
close spaced beams or similar obstructions may
preclude ceiling mounting. It is considered to be the
responsibility of the installer/client to determine if the
presence of asbestos in the ceiling material would
make ceiling mounting 'impractical'.
DON'T place Smoke Alarms in any of the following
areas:
• Bathrooms, kitchens, shower rooms, garages or other
rooms where the smoke alarm may be triggered by steam,
condensation, normal smoke or fumes. Keep at least 6
metres away from sources of normal smoke/fumes.
DON'T place Heat Alarms in any of the following
areas:
• Bathrooms, shower rooms or other rooms where the unit
may be triggered by steam or condensation.
DON'T place Smoke or Heat Alarms in any of the
following areas:
• Places where the normal temperature can exceed 40°C or
be below 4°C (e.g. attics, furnace rooms, directly above
ovens or kettles etc.) as the heat/steam could cause
nuisance/false alarms.

Locations To Avoid

12
SMOKE ALARMS
<600mm
HEAT ALARMS
<150mm
x
APEX
Figure 2
x

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ei160e seriesEi166e

Table of Contents