3.3 Cable Connections

1
2
Section C
Section A
Section B
1. Section A: Inverter communication ports including CAN/RS485 and enable lines
2. Section B: DIP switch for setting communication termination resistor.
3. Section C: DIP switch for setting primary/secondary packs.
4. Section D: Do not connect the internal communication ports
5. Section E: Battery power ports including positive/negative pole and ground
(POS: power terminal plus, NEG: power terminal minus, GND: ground)
3.3.2

Guide for cable connection and setting the DIP switch

1
2
3
4
5
6
3.3.3 Spring Terminal Blocks, when choosing the communication cable
and cable sheath for peeling.
3
Section D
Section E
1. Section A: Inverter communication
ports
a) First, connect the enable ground
wire to Terminal 2.
b) Connect the enable 12V positive
line to Terminal 1.
c) Select the method that matches the
inverter communication method
in the part marked. If the inverter
uses RS485, connect the RS485
(A+, B-) lines to Terminals 3 and 4.
If inverter uses the CAN method,
connect the CAN (high, low) lines
to Terminals 5 and 6.
2. Section B: DIP switch for setting
communication termination resistor
of primary/secondary packs
Lower the DIP switch (Communication
Termination resistor) all downwards for
single pack.
to the appendix about setting for
communication termination resistor.
3. Section C: DIP switch for setting
primary/secondary packs
Raise all DIP switch upward when
you want to use as a primary pack.
And also, when you want to use as a
secondary pack, lower the switch on
the right side only when viewed from
the front
1
2
3
3.3.3

Spring Terminal Blocks

1. Power terminal block
Max. cable length: 10 m
(35 ft)
Cable type: 8mm² (8 AWG)
DC 600V insulated
Pinning
Phoenix contact
PCB terminal block SPT
5/3-H-7,5-ZB
P/N: 1719202
2. Communication terminal block
Max. cable length: 10 m
(35 ft)
Cable type: 0.2~1.5mm²
(18~22AWG)
Pinning
Phoenix contact
PCB terminal block SPT
2,5/6-H-5,0
P/N: 1991011
terminal cable).
NOTE
the battery and/or inverter.
4. Section E: Battery power port
a) Connect the ground wire to
Terminal 2.
b) Connect the negative line of the
power cable to Terminal 3.
c) Connect the positive line of the
power cable to Terminal 1.
3.3.3 Spring Terminal
Blocks when choosing the battery
power cable and cable sheath for
peeling.
( + )
GND
( - )
ENABLE 12V
ENABLE GND
RS485 A+
RS485 B-
CAN Hi
CAN Lo
18