heat-timer DIGI-Elite SEQ-3 Assembly, Installation And Operation Instructions

Advertisement

Quick Links

INSTALLATION AND OPERATION INSTRUCTIONS
SEQ-3 DIGI-E
Hydronic Multi-Stage Boiler Control
Hot Water Control with Outdoor Reset, Set Point and
2 Line Alphanumeric Display
Displays sensor values and
menu settings
®
SYSTEM =
TARGET =
SYS
A
B
Boiler
Pump
SET
Display Section Locking Screws
This Heat-Timer control is strictly an operating control;
it should never be used as a primary limit or safety
control. All equipment must have its own certified
limit and safety controls required by local codes. The
installer must verify proper operation and correct any
safety problems prior to the installation of this Heat-
Timer control.
DHW for Hydronic Applications
Black (120VAC power)
Output Lights indicate
output status
147F
150F
DHW
C
Pump
R
C O R P O R A T I O N
WARNING
®
The SEQ-3 DIGI-SPAN Elite is a multi-boiler or multi-stage
outdoor reset hydronic heating control. It establishes ambient
comfort by varying the temperature of the heating system's
circulating hot water in response to changes in the outdoor
temperature. In addition, it provides an outdoor temperature
based cutoff, heating system pump control, and domestic hot
water (DHW) pump control. Two unique features have been
added to this control including a customized reset ratio curve.
A Set Point option was added for applications where outdoor
reset will not apply.
Two sensors are used, one to monitor the outdoor temperature
and one to monitor the circulating hot water temperature in
the heating system. When the outdoor temperature falls below
the outdoor cutoff setting, the heating system is activated
and the target water temperature is increased proportionally
to satisfy the load. Should it get warmer outdoors, the target
water temperature is automatically lowered by the control. If
the outdoor temperature continues to rise to the outdoor cutoff
Yellow (Output A)
setting then the heating system is turned off.
Because of the many different physical characteristics of
Blue (Output B)
buildings including the type of radiation; i.e., baseboard or
radiant, the heat loss varies. In one building, a 1-degree
outdoors temperature change may require a change of 1 degree
White (Output C)
in heating water temperature; for another it may require a
change of 2, 3, or even 4 degrees in order to gain the desired
comfort level. This is known as the Reset Ratio. The Reset
Ratio chart shows the wide range of Reset Ratios available for
the SEQ-3 in addition to the customized reset ratio. See page 2.
The installer fits the SEQ-3 to a specific building by adjusting
the Reset Ratio curve. With curve number 4 (2:1 reset ratio)
a 2-degree change in outdoor temperature will change the
circulating target temperature by 1 degree; at curve number
11(1:3 reset ratio) an outdoor change of 1 degree will change
the target temperature by 3 degrees. Most buildings with
baseboard radiation require a curve of 6, 7, or 8. Radiant heat
R
lItE

Advertisement

Table of Contents
loading

Summary of Contents for heat-timer DIGI-Elite SEQ-3

  • Page 1 SEQ-3 in addition to the customized reset ratio. See page 2. WARNING This Heat-Timer control is strictly an operating control; The installer fits the SEQ-3 to a specific building by adjusting it should never be used as a primary limit or safety the Reset Ratio curve.
  • Page 2: Operation Concept

    applications usually require a lower curve. An external T-Stat input can be used to shut 1:4 1:3 1:1.5 the heating system down when the thermostat is satisfied. Another, is a Setback input that 12 11 will switch the heating system to a lower set point determined by the Set Back setting. 1:1.25 Type of Radiation in Building Reset Ratio...
  • Page 3: Mounting The Controller

    120VAC using the two Black wires or 24VAC using the right most two terminals on the terminal block on bottom of the control. Heat-Timer recommends the installation of a Surge Suppressor and a Power Switch before the Power Line connection for safety and ease of service.
  • Page 4: Wiring Outputs

    When connected in that mode, it will be used as an input for the Outdoor Cutoff only. Outdoor Label on back of Sensor Outdoor • Only use the Heat-Timer outdoor sensor (HT# 904220-00). drip-hole Conduit • Place the sensor in the shade on the north side of the building.
  • Page 5 SEQ-3 Digi-Elite Operation Manual Output Mode Table Output A Output B Output C Output Mode Description (Yellow (Blue (White Notes Wires) Wires) Wires) 1-On/Off+1-Pump One On/Off boiler and a System pump Sys Pump Not used Boiler One On/Off boiler, a System pump and 1-On/Off+2-Pump Sys Pump Boiler...
  • Page 6 Pump ply the pumps with power and the control can break the hot leg. Boiler 3 • Heat-Timer recommends not sharing the power (White/ source to the control with any pumps, boilers, Output C) C O R P O R A T I O N or heavy electric equipment.
  • Page 7 SEQ-3 Digi-Elite Operation Manual Menus Startup Menu HEAT-TIMER CORP. DIGI-SPAN ELITE Loading Default DISPLAY UNIT: V1.00 c 2006 SEQ-3 Values... -OUTPUT MODE-- SENSOR FAULT: CONTROL MODE: SETUP COMPLETE! 1-On/Off+1-Pump Output On Outdoor Reset PRESS SET 1-On/Off+2-Pump Output Off Set Point...
  • Page 8: Startup Options

    Button and Navigating Menus The SEQ-3 has three buttons. • The SET button function varies. When the Default Screen is displayed, pressing the SET Button views the MENU. When in the Menus and settings, the SET Button accepts the selected entry or setting value.
  • Page 9: Default Display

    SEQ-3 Digi-Elite Operation Manual Outdoor Reset Mode • When Output-On is selected, the SEQ-3 will energize all boiler and system relays when the System reads SHORT or OPEN and Outdoor is below Outdoor Cutoff. Thus, all boilers will run on their limits. However, if the Outdoor sensor fails and the Outdoor reads SHORT or OPEN, the SEQ-3 will change the Target Set Point to the Max Water Temperature.
  • Page 10 • If required: Adjust the RESET RATiO in cold weather. If the ambient building temperatures are too cold in cold weather, move the ratio to a higher selection. That is, if 1.00 (O):1.00 (S) was initially selected, change the selection to 1.00 (O):1.25 (S). If the building temperatures are too warm in cold weather, move the ratio to a lower selection.
  • Page 11 SEQ-3 Digi-Elite Operation Manual Minimum Target (Available when Startup Control Mode = Outdoor Reset) Options: From 70ºF/21ºC to 170ºF/77ºC Default: 80ºF/27ºC Min Target: /Set Point/<Out. Reset>/Min. Tgt 120 F • The Minimum Target Temperature must be set to the boiler manufacturer’s specification. The SEQ-3 will calculate the Target based on the Outdoor temperature, the Reset Ratio, and the Offset value.
  • Page 12 Minimum Runtime Minimum Runtime: Options: 1 to 60 minutes Default: 2 minutes /<Settings>/<Stage>/Min. Runtime • This is the minimum amount of time any stage will run. • The Minimum Runtime for the lowest firing stage on a boiler starts after the purge cycle. •...
  • Page 13 +0 F /<Maintenance>/Sys. Trm or Out. Trim • The Heat-Timer sensors are very accurate. However, sometime it might be beneficial to adjust Outdoor Trim: the values to match and existing system. The System and Outdoor Trim values adjust the System +0 F Sensor and Outdoor Sensor readings using positive or negative values.
  • Page 14: Troubleshoot

    Troubleshoot No Display or LED Lights Check the power to the SEQ-3. The SEQ-3 requires 120VAC power to the Black wires or 24VAC to the right-most terminals. Turn the power off and back on to restore the display. If unsuccessful, make sure that the control's Display Cover is securely mounted to the Base.
  • Page 15 Aquastat relays. A power source must supply pumps with power and the control can break the hot leg. Boiler • Heat-Timer recommends using a separate power source to the control from any pumps, boilers, heavy electric equipment. Indirect • When wiring a sensor to the SEQ-3, connect the Shield to the COM terminal on the SEQ-3 end.
  • Page 16: Specifications

    Setback Input: ..........Terminals P+, P- 20 New Dutch Lane, Fairfield, NJ 07004 973-575-4004 • Fax 973-575-4052 • http://www.heat-timer.com...