Outdoor Unit:
Compressor
Type
Compressor model
Nominal output
Compressor oil...Amount
Coil resistance (Ambient temp. 25°C)
Safety devices
Run capacitor
Crank case heater
Fan & Fan Motor
Type
Q'ty ....... Dia.
Fan motor model...Q'ty
No. Of poles...rpm (230 V, High)
Nominal output
Coil resistance (Ambient temp. 20 °C )
Safety devices
Run capacitor
Heat Exch. Coil
Coil
Rows
Fin pitch
Face area
External Finish
GRV220C5TA-
Type
Overload relay
Operating Temp. Open
Close
Operating amp.(Ambient temp.25°C)
Type
Operating temp. Open
Close
W
cc.
Internal protector
-
°C
Automatic opening
Automatic reclosining
°C
-
µF
VAC
KFC6S-51B5P
W
°C
°C
µF
VAC
Aluminium plate fin / Copper tube
mm
2
m
Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
14
Rotary (Hermetic)
80244035 C-RN220H5A
2200
FV68S...1350
C-R: 0,777
C-S: 2,408
External protector
OL-D24
150 ± 5
63 ± 10
Trip in 6 to 16 sec.at 59 A
40
400
240 V - 30 W
Propeller
1.... Ø 460
KFG6S-51SA5P - 1
OR /
6...860 / 6...856
50 / 62,6
BRN-WHT: 95,9 / 98,1
WHT-YEL: 55,4 / 56,7
YEL - PNK : 7,2 / 7,4
Internal thermal protector
130 ± 5
83 ± 15
5,0
440
2
2
0.610