T300MVi Specifications
Item
Voltage Class
Drive Rating (A):
62
4160 Drive Output (kVA):
447
536
Nominal HP 4160 V**
500
600
Dimensions H x W x D (in)
Voltage Class
Drive Rating (A):
64
2400 V Drive Output (kVA):
268
313
Nominal HP 2400 V**
300
350
Dimensions H x W x D (in)
Output Frequency (Hz)
0 to 120 Hz
Main Circuit
Three-Phase 4160 V Input Isolation Transformer 24-Pulse Design with Input-Fused Disconnect and Vacuum Contactor, IGBT Output
Control Circuit
Integral to Main Transformer; Includes 120 V and 460 V
Tolerance
Voltage: ± 10%; Frequency ± 5%
Control Method
Multi-Level Pulse Width Modulated (PWM) Output Control
Frequency Precision
Analong Input: ± 0.5% of Maximum Output Frequency; Digital Input: 0.01%
V/F Control
V/Hz, Sensorless Vector Control, Variable Torque, Closed-Loop Vector Control, Constant Torque (Option)
Acceleration/Deceleration
0.1 to 6000 Seconds
Soft Stall (Automatic Load Reduction Control During Overload)
Main Control Functions
Restart into Rotating Motor
Main Protective Functions
Current Limit, Overcurrent, Overcharge, Overload, Undervoltage, Overvoltage, Ground Fault, CPU Error, Abnormal Cooling Fan
Data Transmission
Ethernet, Optional Profibus, Modbus RTU, Modbus, TCP/IP, TOSLINE-S20, and DeviceNet Available
Overload Ratio
115% FLA for 60 Seconds (2000 HP, 4160 V, 110%)*
Liquid Crystal Display/
4 x 20 Graphical Backlit LCD Display; Ability to Display Multiple Parameters on One Screen; Flash-Upgradeable Software Includes Multi-Function Ro tary Encoder
Electronic Operator
and Ethernet PC Interface
(LCD EOI )
LED Indications
Run (Red)/Stop (Green), Remote/Local, Indication of Inverter Status
Keys
Local/Remote, Monitor/Program, Run, Enter, ESC, Stop/Reset, Up, Down
Push Button
Illuminated Interlock and Fault Reset Push Buttons
Analog Outputs
Eight Selectable Voltage or Current Output Signals with Programmable Functions
Analog Inputs
Two Selectable Voltage or Current Input Signals
Digital Inputs
Eight Digital Inputs with Programmable Functions
Digital Outputs
Six Available Digital Outputs with Programmable Functions (One Internal to Drive)
Enclosure
NEMA 1, IP20, IEC-529, Gasketed and Filtered
Panel Construction
Free-Standing, Front Maintenance Type, Top or Bottom Access for Motor and Power Cables
Cooling
Forced-Air Cooled with Optional Redundant Fans
Color
ANSI-61 Gray
Ambient Temperature
0 to 40˚; 32 to 104˚F
Humidity
Maximum 95% (Non-Condensing)
Altitude
1000 Meters Above Sea Level or Less
Installation
Indoor, No Direct Sunlight, Protect from Corrosive Gases, Explosive Gases
Typical Applications
Fan, Blower, Pump, Compressor, Extruder, Options for Submersible Pumping Applications
Standards
Electrical Performance: NEC, ANSI
Components and Others
NEC, NEMA, UL
Standard Specifications
74
87
99
112
124
625
715
804
893
700
800
900
1000
104 x 74 x 44
75
86
97
107
129
357
402
447
536
400
450
500
600
104 x 74 x 44
Power Requirements
Control Specifications Input
Ambient Conditions
**Typical HP Rating of 4-Pole Motor; Contact Factory for Applications on Constant Torque Loads
4160 V
155
186
217
248
1116
1340
1563
1786
1250
1500
1750
2000*
104 x 122 x 44
2400 V
150
172
193
215
625
715
804
893
700
800
900
1000
104 x 122 x 44
Interface
Construction
279
310
372
434
496
2010
2233
2680
3126
3573
2250
2500
3000
3500
4000
104 x 1 64 x 50
104 x 174 x 50
104 x 222 x 50
269
322
376
430
504
1116
1340
1563
1786
2010
1250
1500
1750
2000
2250
104 x 174 x 50
104 x 222 x 50
558
620
4019
4466
4500
5000
537
2233
2500

Advertisement