8. Operation Details

8.1. Cooling Mode Operation
Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
- When the compressor is stopped by Remote Control, it restarts
after 3 minutes when it is turned ON by Remote Control.
- When the setting temperature is reached during cooling operation,
the compressor stops and it will not start for 3 minutes.
7 minutes Time Save Control
- The compressor will start automatically if it has stopped for 7
minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
Starting Current Control
- When the compressor, outdoor fan motor & indoor fan motor are
simultaneously started, the indoor fan motor will operate 1.6
second later.
Anti-Freezing Control
- If the temperature of the indoor heat exchanger falls continuously
below 2°C for 4 minutes or more, the compressor turns off to
protect the indoor heat exchanger from freezing. The fan speed
setting remains the same.
- Compressor will restart again when the indoor heat exchanger
temperature rises to 10°C (Recovery).
19