Flushed Finishing & Framing With Non Combustible Material; Non Combustible Requirements - Regency Fireplace Products Greenfire GF1500L Owners & Installation Manual

Table of Contents

Advertisement

installation
Flushed Finishing & Framing with Non Combustible Material
Finished
* diagrams shown below are
Material
with top nailing strip removed.
12mm
25mm
38mm

Non Combustible Requirements

Timber Stud
16
|
Greenfire® GF1500L-2 Gas Fireplace
Unit
Unit
Unit
1432 mm
Non-Combustible
Material
A minimum thickness of 12mm non-
combustible facing is required.
Non-combustible
Combustible
Material
• For flush finishing, the top nailing strip must be removed and a non-combustible
steel stud support added.
The seven fireplace opening standoffs which are located on this unit can be removed
when non combustible material is installed flush with the unit.
(see P. 13).
Non-combustible finishing material on the top and sides must also be used.
MINIMUM THICKNESS OF THE FINISH MATERIAL: 12MM
Steel Stud
on edge
Timber Stud
• The appliance must be installed on
a flat, solid, continuous surface For
example a wood, metal or concrete
floor. In a raised (on the wall)
application the appliance must be
installed on a metal or wood panel
extending the full width and depth of
the appliance.